Additional Charge
MCAC-UTSM-2008-11
130
Installation
Special vacuum dry procedure
②
l
This vacuum dry method is used in the following conditions:
l
There
’
s moisture when flushing the refrigerant pipe.
l
Rainwater may enter into the pipe.
l
Vacuum dry for the first time
······
2h pumping
. Vacuum destroy for the se
③
cond time
······
Fill nitrogen to 0.5Kgf/cm2
Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is
too much, this method can
’
t dry thoroughly. So, please pay more attention to prevent water entering and
forming condensation water.
. Vacuum dry for the second time
······
1h pumping
④
Determinant: Pass if achieving below -755mmHg. If -755mmHg can
’
t be achieved in 2h, repeat procedure
③
and
.
④
. Vacuum placing test
······
1h
⑤
. Sketch map of special vacuum dry procedure
⑥
3. Additional Charge
Caution
●
Refrigerant cannot be charged until field wiring has been completed.
●
Refrigerant may only be charged after performing the leak test and the vacuum pumping.
●
When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.
●
Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the
appropriate refrigerant is charged.
●
Refrigerant containers shall be opened slowly.
●
Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the
diameter and the length of the liquid side pipe of the outdoor unit/indoor unit
R(g) D(mm)
L(m)
φ
6.4
Φ
9.5
Φ
12.7
Less than 5m (One-way)
—
—
—
Added Refrigerant When
Over 5m(One-way)
11g/m
×
(L-5)
30g/m
×
(L-5)
60g/m
×
(L-5)
Remark:
R(g): Additional refrigerant to be charged
L(m): The length of the refrigerant pipe(one-way)
D(mm): Liquid side piping diameter
Содержание MCA-12HRN1
Страница 2: ......
Страница 13: ...MCAC UTSM 2008 11 Dimensions Indoor Units 11 3 Dimensions 4 Service Space...
Страница 14: ...Wiring Diagram MCAC UTSM 2008 11 12 Indoor Units 5 Wiring Diagram...
Страница 21: ...MCAC UTSM 2008 11 Field Wiring Indoor Units 19 13 Field Wiring MCA 12HRN1...
Страница 22: ...Field Wiring MCAC UTSM 2008 11 20 Indoor Units MCA 18HRN1...
Страница 31: ...MCAC UTSM 2008 11 Wiring Diagrams Indoor Units 29 5 Wiring Diagrams 5 1 MCC 24HRN1 MCC 30HRN1 MCC 36HRN1...
Страница 32: ...Wiring Diagrams MCAC UTSM 2008 11 30 Indoor Units 5 2 MCC 30HRN1 R MCC 36HRN1 R MCC 48HRN1 R...
Страница 41: ...MCAC UTSM 2008 11 Exploded View Indoor Units 39 10 Exploded View 10 1 MCC 24HRN1 33...
Страница 43: ...MCAC UTSM 2008 11 Exploded View Indoor Units 41 10 2 MCC 30HRN1...
Страница 45: ...MCAC UTSM 2008 11 Exploded View Indoor Units 43 10 3 MCC 30HRN1 R...
Страница 47: ...MCAC UTSM 2008 11 Exploded View Indoor Units 45 10 4 MCC 36HRN1...
Страница 49: ...MCAC UTSM 2008 11 Exploded View Indoor Units 47 10 5 MCC 36HRN1 R...
Страница 51: ...MCAC UTSM 2008 11 Exploded View Indoor Units 49 10 6 MCC 48HRN1 R 34 3 3 2 3 3 3 4 3 5 3 6 3 7 32 3...
Страница 54: ...Field Wiring MCAC UTSM 2008 11 52 Indoor Units 13 Field Wiring...
Страница 62: ...Service Space MCAC UTSM 2008 11 60 Indoor Units 4 Service Space...
Страница 63: ...MCAC UTSM 2008 11 Wiring Diagrams Indoor Units 61 5 Wiring Diagrams 5 1 MUB 12HRN1 MUB 18HRN1...
Страница 64: ...Wiring Diagrams MCAC UTSM 2008 11 62 Indoor Units 5 2 MUB 24HRN1 MUB 30HRN1 1 phase MUB 36HRN1 1 phase...
Страница 65: ...MCAC UTSM 2008 11 Wiring Diagrams Indoor Units 63 5 3 MUB 30HRN1 3 phase MUB 36HRN1 3 phase...
Страница 66: ...Wiring Diagrams MCAC UTSM 2008 11 64 Indoor Units 5 3 MUB 48HRN1 R MUB 60HRN1 R...
Страница 87: ...MCAC UTSM 2008 11 Field Wiring Indoor Units 85 13 Field Wiring MUB 12HRN1 MUB 18HRN1...
Страница 88: ...Field Wiring MCAC UTSM 2008 11 86 Indoor Units MUB 24HRN1 MUB 30HRN1 MUB 36HRN1 1 phase...
Страница 89: ...MCAC UTSM 2008 11 Field Wiring Indoor Units 87 MUB 30HRN1 MUB 36HRN1 3 phase MUB 48HRN1 R MUB 60HRN1 R...
Страница 96: ...Dimensions MCAC UTSM 2008 11 94 Outdoor Units 2 Dimensions 2 1 MOU 12HN1...
Страница 97: ...MCAC UTSM 2008 11 Dimensions Outdoor Units 95 2 2 MOUA 18HN1...
Страница 98: ...Dimensions MCAC UTSM 2008 11 96 Outdoor Units 2 3 MOUA 24HN1...
Страница 99: ...MCAC UTSM 2008 11 Dimensions Outdoor Units 97 2 4 MOU 30HN1 MOU 30HN1 R MOU 36HN1 MOU 36HN1 R...
Страница 100: ...Dimensions MCAC UTSM 2008 11 98 Outdoor Units 2 5 MOUA 48HN1 R MOUA 60HN1 R...
Страница 105: ...MCAC UTSM 2008 11 Wiring Diagrams Outdoor Units 103 5 Wiring Diagrams 5 1 MOU 12HN1...
Страница 106: ...Wiring Diagrams MCAC UTSM 2008 11 104 Outdoor Units 5 2 MOUA 18HN1...
Страница 107: ...MCAC UTSM 2008 11 Wiring Diagrams Outdoor Units 105 5 3 MOUA 24HN1...
Страница 108: ...Wiring Diagrams MCAC UTSM 2008 11 106 Outdoor Units 5 4 MOU 30HN1 MOU 36HN1...
Страница 109: ...MCAC UTSM 2008 11 Wiring Diagrams Outdoor Units 107 5 5 MOU 30HN1 R MOU 36HN1 R...
Страница 110: ...Wiring Diagrams MCAC UTSM 2008 11 108 Outdoor Units 5 6 MOUA 48HN1 R MOUA 60HN1 R...
Страница 128: ......
Страница 138: ...Control MCAC UTSM 2008 11 136 Control Part 5 Control 1 Remote Controller 137...