9.2.5 Over current protection occurs 4 times diagnosis and solution
No
Correct the operation condition.
Check if the voltage of the
power supply is too low?
Yes
Repair the power supply.
Is the outdoor
operation temperature
too high? Does the
outdoor unit has bad
air circulation?
Yes
No
Check if the outdoor
fan can run properly?
No
Correct the connection of fan
motor or replace the fan motor.
Yes
Yes
Check if the compressor
is normal running
No
Replace the
compressor
Yes
Replace the capillary.
Evacuate the system
and recharge refrigerant.
Disconnect with the power
and replace the main PCB.
Turn on the units and check
if the problem remains
Содержание MA9A-24HR-QB4W
Страница 19: ...17 MS9A 18CR QB6...
Страница 20: ...18 MS9A 18CR PC4W A MS9A 05CR QD0 MS9A 09CR QB6 A MS9A 09CR QB6 MS9A 09CR QC0 MS9A 09CR QC4 A...
Страница 21: ...19 MS9A 12CR QC4 A MS9A 18CR QC0 MS9A 18CR QC2 MS9A 18CR QB8 MS9A 18CR QC4 A MS9A 18CR QC0 A...
Страница 22: ...20 MS9A 21HR QB6W MA9A 24HR QB4W MS9A 22CR QC0 MS9A 22CR QB8...
Страница 23: ...21 5 2 Outdoor Units MOK2 07C QB6 MOK6 09C QB6 MOA1 12C QB6 MOA2 12C QB6...
Страница 24: ...22 MOB 18C QB6...
Страница 25: ...23 MOK 07H QB6 MOK3 09H QB6 MOB 12H QB6 MOA1 12H QB4 MOA2 12H QB6...
Страница 26: ...24 MOK 05CP QD0 MOK8 09C QB6 MOK9 09C QB6 MOB1 09C QC0 MOB1 09C QC4 MOB2 12C QC4 MOF 18C QC2 MOF2 18C QC4...
Страница 27: ...25 MOB3 18C QB8 MOC2 18C QC0 MOB1 18CP QC0 MOB2 18CP QC0...
Страница 28: ...26 MOB 18H QB6...
Страница 29: ...27 MOF 18C QC4W MOF4 21H QB6W...
Страница 30: ...28 MOF 22C QC0 MOF 22C QB8 MOF 24H QB4...