Symptom
Probable reason
Check items or handling methods
Air suction and
exhausting pressure
have no difference
after operation.
Reverse the compressor or inner air
mixed up.
When the compressor was reversed, change
any two L wires. Inner air mixed up, change
the compressor, Check the leakage and
maintain, and add refrigerant, change the
drier-filter.
Symptom
Probable reason
Check items or handling methods
High air exhausting
temperature
Refrigerant leakage.
Check whether the leakage and maintain, and
add refrigerant.
Symptom
Probable reason
Check items or handling methods
High air exhausting
pressure
Condenser has been blocked.
Clean the condenser.
Condenser fan cannot run.
1, Check the wiring was correct or not.
2, Check whether it has 3~10V DC between
wire 22 and wire 05. If has, the outdoor
inverter is error. And if no, check the indoor
unit controller.
Too much refrigerant adding amount.
Fasten the connection.
Symptom
Probable reason
Check items or handling methods
Low air
suction
pressure or
return liquid.
Lack of refrigerant in system.
Check the leakage and maintain, add
refrigerant.
Air filter too dirty
Change the air filter.
Drier-filter is blocked.
Change the drier-filter.
Non-correct overheat adjustment
Strictly accord to the adjustment steps to
adjust the thermal expansion valve.
Expansion valve error.
1, Check the temperature sensor and the
balance pipe whether have leakage.
2, Check the expansion valve whether has
serious frosting.
Condensed pressure too low
Check the fan operates normally or not.
Belt creep
Check the belt and adjust it.
Symptom
Probable reason
Check items or handling methods
Large
compressor
noise.
Return liquid.
Refers to Low air suction pressure or return
liquid.
Lubricating oil lost and cause bearing
damaged.
Add the lubricating oil.
Compressor or pipe line is loose.
Fasten the connection.
Common faults and handling methods of outdoor fan system
Both error and alarm are the abnormal working states of inverter. But there are different. Inverter
will self-check during operation. If there is error, the inverter will display error code, and cut off
All manuals and user guides at all-guides.com
all-guides.com