DM15-01.01.11-01en
Service manual
Multi DC inverter R410A. Outdoor unit
45
36
AD value of voltage
For example ,the digital display tube show “Cd”, it means AD value is
205.
37
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display tube will show single
digit and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV
open angle is 120×4=480p.)
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42 Frequency
limit
symbol
Bit7
Frequency limit caused by IGBT
radiator
The display value
is hex number. For
example, the
digital display tube
show 2A,then
Bit5=1, Bit3=1,
Bit1=1.
It means
frequency limit
caused by T4,T3
and current.
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
43
Average value of T2
(Sum T2 value of all indoor units)/( number of indoor units in good
connection)
44
Outdoor unit fan motor state
Off:0, High speed:1, Med speed:2, Low speed:3 Breeze:4, Super
breeze:5
45
The last error or protection code
00 means no malfunction and protection
The following items from 9.4.1 to 9.4.5 are for the explanation of the point check functions.
10.4.1 Frequency of compressor:
Display
Frequency of compressor (Hz)
30 30
-- Stand
by
60 60
10.4.2 Running mode:
Display
Corresponding mode
0 Off
1 Fan
only
2 Cooling
mode
3 Heating
mode
4 Forced
cooling
10.4.3 Capacity demand:
Cooling mode
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b