MCAC-HTSM-2007-11
Control function
Control System
143
1.1.4.8 No. 1 opening degree of electronic expansion valve:
Opening degree equals the display data times 8
1.1.4.9 No. 2 opening degree of electronic expansion valve:
Opening degree equals the display data times 8
1.1.4.10 No. 3 opening degree of electronic expansion valve:
Opening degree equals the display data times 8
1.1.5 Protection
1.1.5.1 3 minutes delay at restart for compressor.
1.1.5.2 Discharge temperature protection of compressor, compressor stops when the temp. of discharge is
more than 115
°
C and last out 5 s. compressor runs when the temp. of discharge is less than 90
°
C.
1.1.5.3 Temperature protection of compressor top, compressor stops when the temp. of top of compressor
is more than 120
°
C, compressor runs when the temp. of top of compressor is less than 105
°
C.
1.1.5.4 When AC voltage
≥
270V for 30 seconds, Outdoor Unit stops operation and alarms. When AC
voltage
≤
260V for 30 seconds, Outdoor Unit resumes operation.
1.1.3.5 Inverter module Protection , Inverter module Protection itself has a protection function against
current, voltage and temperature.
1.1.5.6 Sensor protection at open circuit and breaking disconnection
1.1.5.7 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can
’
t return to
normal operation automatically.
1.1.5.8 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and
LED displays failure information and can
’
t return to normal operation automatically. (only available
for wall mounted indoor unit)
1.1.5.9 Current protection: When the current is more than 20A, the compressor stops.
1.1.5.10 Outdoor condenser high temperature protection: Under cooling mode, if T3>65
°
C for 3 minutes, the
compressor will stop. When T3<52
°
C, the protection is not valid.
1.1.5.11 Outdoor low temperature protection: If the outdoor temperature is lower than -15
°
C for 1 hour, the
compressor and fan motor will stop. If the outdoor temperature is higher than -12
°
C for 10 minutes
and the compressor stops operation for 1h, or the outdoor temperature is higher than 5
°
C for 10
minutes, then restart and enter into the prior operation mode.
1.1.5.12 Compressor pre-heating function: When the outdoor temperature is lower than 3
°
C and the
compressor stops operation for more than 3 hours, or the outdoor temperature is lower than 3
°
C
and the power is just put on, the compressor enters into pre-heating condition. When outdoor temp.
is more than 5
°
C or user operate it, pre-heating condition will finish.
1.1. 6
Fan-only mode
Fan speed is high/mid/low/ Auto
1.1.7
Cooling mode
1.1.7.1 Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto:
1.1.7.2 Auto fan at cooling mode: (T=Indoor Temp.-Setting Temp.)
Condition
Indoor fan speed
Room temp. up
T<1.5
°
C
Low
1.5
°
C
<T<4
°
C
Mid.
T>4
°
C
High
Room temp. down
T> 3
°
C
High
1
°
C
<T<3
°
C
Mid.
T<1
°
C
Low
Содержание M2OA-18HRDN1
Страница 2: ......
Страница 22: ...Wall mounted Type MCAC HTSM 2007 11 20 Indoor Units l Indoor Unit MSCI 12HRIN1...
Страница 24: ...Wall mounted Type MCAC HTSM 2007 11 22 Indoor Units 3 3 Vertu Series Indoor unit MSV1I 09HRDN1 MSV1I 12HRDN1...
Страница 27: ...MCAC HTSM 2007 11 Wall mounted Type Indoor Units 25 4 Service Space...
Страница 29: ...MCAC HTSM 2007 11 Wall mounted Type Indoor Units 27 5 3 MST6I 07HRIN1 MST6I 09HRIN1 MST6I 12HRIN1...
Страница 50: ...Four way Cassette Type MCAC HTSM 2007 11 48 Indoor Units 4 Service Space unit mm...
Страница 59: ...MCAC HTSM 2007 11 Four way Cassette Type Indoor Units 57 10 Accessories...
Страница 65: ...MCAC HTSM 2007 11 Duct Type Indoor Units 63 4 Service Space...
Страница 79: ...MCAC HTSM 2007 11 Ceiling and Floor Type Indoor Units 77 4 Service Space Ceiling type installation 600mm 600mm...
Страница 80: ...Ceiling and Floor Type MCAC HTSM 2007 11 78 Indoor Units 5 Wiring Diagrams MSDLI 12HRIN1 MSDLI 18HRIN1...
Страница 82: ...Ceiling and Floor Type MCAC HTSM 2007 11 80 Indoor Units Discharge angle 60 FLOOR Airflow velocity Temperature...
Страница 94: ...Service Space MCAC HTSM 2007 11 92 Outdoor Units 4 Service Space...
Страница 96: ...Wiring Diagrams MCAC HTSM 2007 11 94 Outdoor Units 6 Wiring Diagrams M2OA 18HRDN1 M3OA 27HRDN1 M2OB 18HRDN1...
Страница 97: ...MCAC HTSM 2007 11 Wiring Diagrams Outdoor Units 95 M4OA 27HRDN1...
Страница 101: ...MCAC HTSM 2007 11 Field Wiring Outdoor Units 99 8 Field Wiring...
Страница 141: ...MCAC HTSM 2007 11 Control System Control System 139 Part 5 Control System 1 Control function 140 2 Control device 149...
Страница 152: ...Control device MCAC HTSM 2007 11 150 Control System...
Страница 153: ...MCAC HTSM 2007 11 Control device Control System 151...
Страница 155: ...MCAC HTSM 2007 11 Control device Control System 153...
Страница 157: ...MCAC HTSM 2007 11 Control device Control System 155...
Страница 158: ...Control device MCAC HTSM 2007 11 156 Control System...