Troubleshooting
Outdoor Units
125
Display
Malfunction or Protection
P6
Condenser high temperature protection
When Condenser high temp. is more than 65
°
C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52
°
C.
Remark:
1. Test digital discharge temperature, outdoor condenser temperature T3
2. Test system pressure
3. High digital discharge temperature is likely owing to the lack of refrigerant, air leakage or
system blockade. Check the above items respectively to solve the problem.
4. Condenser high temperature protection owes to the overcharge of refrigerant, air leakage
or bad ventilation and heat-emission conditions.
No
Yes
No
Yes
No
Is the Condenser high temp. more than 65
°
C ?
Is the Condenser high temp. sensor right according to the annex 1.
Replace the outdoor main board
Replace the outdoor pipe temp sensor
The outdoor temp. is too high(More
than 43
℃
)
The system is blocked?
Or EXV is invalid?
Correct the problem or replace the
EXV.
Yes
Содержание M2OA-18HRDN1
Страница 2: ......
Страница 22: ...Wall mounted Type MCAC HTSM 2007 11 20 Indoor Units l Indoor Unit MSCI 12HRIN1...
Страница 24: ...Wall mounted Type MCAC HTSM 2007 11 22 Indoor Units 3 3 Vertu Series Indoor unit MSV1I 09HRDN1 MSV1I 12HRDN1...
Страница 27: ...MCAC HTSM 2007 11 Wall mounted Type Indoor Units 25 4 Service Space...
Страница 29: ...MCAC HTSM 2007 11 Wall mounted Type Indoor Units 27 5 3 MST6I 07HRIN1 MST6I 09HRIN1 MST6I 12HRIN1...
Страница 50: ...Four way Cassette Type MCAC HTSM 2007 11 48 Indoor Units 4 Service Space unit mm...
Страница 59: ...MCAC HTSM 2007 11 Four way Cassette Type Indoor Units 57 10 Accessories...
Страница 65: ...MCAC HTSM 2007 11 Duct Type Indoor Units 63 4 Service Space...
Страница 79: ...MCAC HTSM 2007 11 Ceiling and Floor Type Indoor Units 77 4 Service Space Ceiling type installation 600mm 600mm...
Страница 80: ...Ceiling and Floor Type MCAC HTSM 2007 11 78 Indoor Units 5 Wiring Diagrams MSDLI 12HRIN1 MSDLI 18HRIN1...
Страница 82: ...Ceiling and Floor Type MCAC HTSM 2007 11 80 Indoor Units Discharge angle 60 FLOOR Airflow velocity Temperature...
Страница 94: ...Service Space MCAC HTSM 2007 11 92 Outdoor Units 4 Service Space...
Страница 96: ...Wiring Diagrams MCAC HTSM 2007 11 94 Outdoor Units 6 Wiring Diagrams M2OA 18HRDN1 M3OA 27HRDN1 M2OB 18HRDN1...
Страница 97: ...MCAC HTSM 2007 11 Wiring Diagrams Outdoor Units 95 M4OA 27HRDN1...
Страница 101: ...MCAC HTSM 2007 11 Field Wiring Outdoor Units 99 8 Field Wiring...
Страница 141: ...MCAC HTSM 2007 11 Control System Control System 139 Part 5 Control System 1 Control function 140 2 Control device 149...
Страница 152: ...Control device MCAC HTSM 2007 11 150 Control System...
Страница 153: ...MCAC HTSM 2007 11 Control device Control System 151...
Страница 155: ...MCAC HTSM 2007 11 Control device Control System 153...
Страница 157: ...MCAC HTSM 2007 11 Control device Control System 155...
Страница 158: ...Control device MCAC HTSM 2007 11 156 Control System...