Procedure
4.21.4
Pd
Air side heat exchanger refrigerant outlet
temperature sensor is loose
1
Yes
Ensure the temperature sensor is
connected properly
No
Air side heat exchanger refrigerant outlet
temperature sensor has short-circuited
or failed
2
Yes
Replace the temperature sensor
No
The air side heat exchanger heat
exchange is poor
3
Yes
Inspect the system and fix the error
No
The fan or fan motor is blocked or
damaged
Yes
Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connection port are CN9 on the outdoor unit
refrigerant system main PCB (labeled 6 in Figure 4-2.2)
2.
Set a multi-meter to buzzer mode and test any two terminals of sensor. If the resistance is too low, the buzzer sounds, which means the sensor has
short-circuited. If the resistance is not consistent with the sensor s resistance characteristics table, the sensor has failed. Refer to Table 4-5.1.
3.
Check air side heat exchanger, fan and air outlets for dirt/blockages.
4.
High pressure switch connection is port CN31 on the outdoor unit refrigerant system main PCB (labeled 21 in Figure 4-2.2)
Midea CAC Confidential
Содержание M thermal A Mono Series
Страница 1: ...M thermal A Series Mono 18 30kW Commercial Air Conditioners R32 Service Manual Midea CAC Confidential ...
Страница 3: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential ...
Страница 11: ...M thermal Mono 10 202008 Midea M thermal Mono Service Manual Midea CAC Confidential ...
Страница 25: ...M thermal Mono 24 202008 Midea M thermal Mono Service Manual Midea CAC Confidential ...