4.7 EE Troubleshooting
Digital display output
4.7.1
Description
4.7.2
Hydronic system main PCB EEPROM error.
M thermal Mono stops running.
Error code is displayed on hydronic system main PCB and user interface.
Possible causes
4.7.3
Hydronic system main PCB EEPROM is not connected properly.
Hydronic system main PCB damaged.
Procedure
4.7.4
EE
Hydronic system main PCB EEPROM
1
is
not connected properly
Yes
Ensure the EEPROM is connected
properly
No
Replace hydronic system main PCB
Notes:
1.
Hydronic system main PCB EEPROM is designated IC39 on the main PCB for hydronic system (labeled 31 in Figure 4-2.1).
Midea CAC Confidential