OUTDOOR UNIT DIAGNOSTIC GUIDES
Table 11—Diagnostic Guides
OPERATION LAMP
TIMER LAMP
DISPLAY
LED STATUS
☆
1 time
X
E0
Indoor unit EEPROM parameter error
☆
2 times
X
E1
Indoor / outdoor units communication error
☆
3 times
X
E2
Zero-crossing signal detection error
☆
4 times
X
E3
Indoor fan speed has been out of control
☆
5 times
X
E4
Indoor room temperature sensor T1 open circuit or short circuit
☆
6 times
X
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
☆
7 times
X
EC
Refrigerant leakage detection
☆
1 time
O
F0
Overload current protection
☆
2 times
O
F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
☆
3 times
O
F2
Condenser coil temperature sensor T3 open circuit or short circuit
☆
4 times
O
F3
Compressor discharge temperature sensor T5 open circuit or short circuit
☆
5 times
O
F4
Outdoor unit EEPROM parameter error
☆
6 times
O
F5
Outdoor fan speed has been out of control
☆
1 time
☆
P0
IPM malfunction or IGBT over-strong current protection
☆
2 times
☆
P1
Over voltage or over low voltage protection
☆
3 times
☆
P2
High temperature protection of IPM module or compressor top
☆
4 times
☆
P3*
Outdoor ambient temperature too low.
☆
5 times
☆
P4
Inverter compressor drive error
☆
6 times
☆
P5
Indoor units mode conflict (multi-zone ONLY)