32808001101
19
Specifications subject to change without notice.
a
b
c
d
T1
e
Fig. 23
-
Auto Fan Action in HEATING Mode
DEFROST Mode
The air conditioner enters the DEFROST mode according to the T3
temperature value and the T3 temperature change value range plus the
compressor running time.
During the DEFROST mode, the compressor continues to runs, the
indoor and outdoor motors stop, and the indoor unit defrost lamp
illuminates and
appears.
If any one of the following items is satisfied, the defrosting finishes and
the machine reverts to the normal heating mode.
−−−−T3 rises to be higher than TCDE1
_
C.
−−−−T3 keeps to be higher than TCDE2
_
C for 80 seconds.
−−−−The machine has run for 15 minutes in defrosting mode.
Evaporator Coil Temperature Protection
TEstop
T2
Resume
Off
Decrease
TEdown
TEH2
Hold
Fig. 24
-
Evaporator Coil Temperature Protection
NOTE: The following applies to Fig. 24:
S
Off: Compressor stops
S
Decrease: Decrease the running frequency to the lower level
S
Hold: Keep the current frequency
S
Resume: No limitation for frequency
When the evaporator temperature is higher than the setting protection
value, the compressor stops.
Auto−Mode
This mode can be chosen with the remote controller and the setting
temperature can be changed between 62.6
_
F(17
_
C)~86
_
F(30
_
C).
In the AUTO mode, the machine chooses the COOLING, HEATING
or FAN−ONLY mode according to
Δ
T (
Δ
T =T1−Ts).
Table 8—Auto Mode
ΔT=T
1
-Ts
Running mode
ΔT
>
2
℃
Cooling
-
2
≤ΔT≤
2
℃
Fan-only
ΔT<-
2
℃
Heating
The indoor fan runs under auto fan in the relevant mode. The louver
operates same as in relevant mode. If the machine switches mode
between HEATING and COOLING, the compressor stops for 15
minutes and then chooses the mode according to T1−Ts. If the setting
temperature is modified, the machine chooses the running function
again.
DRY mode
Indoor fan speed is fixed at breeze and can not be changed.
The louver angle is the same as in the cooling mode.
Low indoor room temperature protection
In the DRYING mode, if the room temperature is lower than 50
_
F
(10
_
C), the compressor stops and does not resume until the room
temperature exceeds 53.6
_
F (12
_
C).
Evaporator anti
*
freezing protection, condenser high temperature
protection and outdoor unit frequency limit are active and are the same
as that in the cooling mode. The outdoor fan operates the same as in
cooling mode.
Forced Operation Function
S
Enter forced operation function: When the machine is off,
press Touch to engage the the Forced Auto Mode. Press
Touch again, within 5 seconds, to engage the Forced Cooling
Mode. In Forced Auto, forced cooling or any other operation
mode, press the touch button to turn off the unit. In the forced
operation mode, all general protections and remote control
are available.
Operation rules:
S
Forced cooling mode: The compressor runs at the F2
frequency and the indoor fan runs as a breeze. After running
for 30 minutes, the unit enters the auto mode as 75.2
_
F
(24
_
C) setting temperature.
S
Forced auto mode: The forced auto mode is the same as the
normal auto mode with a 75.2
_
F (24
_
C) setting temperature.
AUTO−RESTART Function
The indoor unit is equipped with the AUTO−RESTART function,
which is carried out through an auto−restart module. In the event of a
sudden power failure, the module memorizes the setting conditions
prior to the power failure. The unit resumes the previous operation
setting (not including the SWING function) automatically three (3)
minutes after the power returns.
If the memorization condition is the FORCED COOLING mode, the
unit will run in the COOLING mode for 30 minutes and turn to the
AUTO mode at the 75.2
_
F(24
_
C) setting temperature.
If the air conditioner is off before the power turns off and the air
conditioner is required to start up, the compressor delays start up for 1
minute before powering on. In other instances, the compressor waits
three (3) minutes before restarts.