INDOOR UNIT INSTALLATION 

INDOOR UNIT INSTALLATION 

Connect the indoor unit first, then the outdoor unit. 
Do not allow the piping to let out from the back of the indoor unit.

CAUTION

Be careful not to let the drain hose slack.
Heat insulation should be done to the extension drain hose of indoor unit. 
Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper 
side can cause drain pan to overflow inside the unit.
Never intercross nor intertwist the power wire with any other wiring.

Fig.6

4.Drain piping

1. Connect the drain hose as described
    in Fig.6. The drain hose should be 
    inclined downward.
2. When drain hose requires extension, 
    obtain an extension hose commercially
    available. Be sure to thermally insulate
    the indoor section of the extension
    hose. Do not let the drain hose slack.
3. Remove the air filter and pour some 
    water into the drain pan to check
    the water flows smoothly.

Right

Wrong

No trap is permitted.

Minimum cross-sectional area of conductors: 

Rated curr ent 

of appliance

(A)

>3  and   6

>6  and   10

>10  and   16
>16  and   25

>25  and   32

>32  and   40

Nominal cross-sectional 

area

(mm2)

0.75

1

1.5
2.5

4

6

The wire size of power supply cord 
and interconnected wire and the 
current of the fuse or switch are 
determined by the maximum current 
indicated on the nameplate which 
located on the side panel of the unit. 
Please refer to the nameplate before 
selecting the wire size, fuse or switch.

  

The controller of the air conditioner 
designed with a fuse protection 
function under abnormal conditions, 
the specifications of the fuse have 
printed on the circuit board, such as: 
T3.15A/250VAC, T5A/250VAC, etc.

NOTE:

Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse to 
     install the air conditioner and explain to the client until the problem is solved. 
2. Power voltage should be in the range of 90%~110%of rated voltage.
3. The  surge protector and main power switch with a 1.5 times capacity of Max. Current of the unit 
      should be installed in power circuit. Ensure the air conditioner is grounded well.
4. The appliance shall be installed in accordance with national wiring regulations. 

Do not operate 

      your air conditioner in a wet room such as a bathroom or laundry room.

5. An all-pole disconnection device which has at least 3mm clearances in all poles, and have a 
     leakage current that may exceed 10mA, the residual current device(RCD) having a rated 
     residual operating current not exceeding 30mA, and disconnection must be incorporated in the 
     fixed wiring in accordance with the wiring rules.
6. For the unit adopts auxiliary electric heater, keep at least 1 meter away  from the nearest 
    combustible materials. 
7. According to the attached Electrical Connection Diagram  located on the panel of the indoor & 
     outdoor unit to connect the wire.
8. All wiring must comply with local and national electrical codes and be installed by qualified and 
    skilled electricians. 
9. Every wire must be connected firmly. No wire should be allowed to touch refrigerant tubing,
     the  compressor, or any moving parts.
10. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard 
      may also exist. Therefore, be sure all wiring is tightly connected.
9. An individual branch circuit and single receptacle used only for this air conditioner must be 
   available. See the following table for suggested wire sizes and fuse specifications:

Electrical work

5. Connect the cable to the indoor unit

,

                  Before performing any electrical work, turn off the main power to the system.
1. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and 
    interconnected cord type is H07RN-F.
2. Lift the indoor unit panel up, use an sharp end tool like a screw driver to pry the wire cover.
3. Remove the cable clamp. Match wire colours with terminal numbers on indoor and outdoor
    unit s terminal blocks and firmly screw wires to the corresponding terminals.
4. Connect the end of the connection cable fully inserting into the terminal block.
5. Fasten the connection cable with a cable clamp.

NOTE:

 The wiring connection is differ from appliance to appliance.(see page 12)

    

NOTE:

Connect the cable to the indoor unit

Terminal block

Wire cover

Screw

Screw driver

Cable clamp

Fig.7

Содержание CS337I-BPMB

Страница 1: ...y and keep it for future reference ROOM AIR CONDITIONER The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer f...

Страница 2: ...n independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 6 Use the specified cable an...

Страница 3: ...lation drawings Do not place any obstacles which may cause a short circuit of the discharged air Select a location which avoids causing a nuisance to neighbours from noise and air emissions from devic...

Страница 4: ...ensed water from rear of the indoor unit is gathered in ponding box and is piped out of room Do not put anything else in the box Fig 4 1 For the left hand and right hand piping remove the pipe cover f...

Страница 5: ...rrent ofthe unit should be installed in power circuit Ensurethe air conditioner is groundedwell 4 The appliance shall beinstalled in accordance with nationalwiring regulations Do not operate your air...

Страница 6: ...rection where the discharged air is not blocked In the case that the installation place is exposed to strong wind such as a seaside make sure the fan operating properly by putting the unit lengthwise...

Страница 7: ...en it with a spanner and torque wrench as shown in Fig 16 17 2 Tightening Connection Excessive torque can break nut depending on installation conditions Indoor unit tubing Flare nut Pipings Fig 16 Out...

Страница 8: ...the AUTO or COOL the unit will operate under Forced AUTOor COOL mode see User Manual for details 4 The testoperation should last about 30 minutes When relocate the unit to another place perform evacua...

Отзывы: