35
8.4.7.7 The tolerance of timer is 1 minute per hour.
8.4.8 Sleep function mode
8.4.8.1 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off.
8.4.8.2. Operation process in sleep mode is as follow:
After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode.
When cooling, the setting temperature rises 1
℃(be lower th
setting temperature stops rising and indoor fan is fixed as low speed.
When heating, the setting temperature decreases 1
℃(be higher than 17℃) e
ur, 2 hours
later the setting temperature stops decreasing and indoor fan is fixed as low speed.(Anti-cold wind
function has the priority)
8.4.8.3 Timer setting is available
8.4.8.4 When user uses timer off function in sleep mode (or sleep function in timer off mode), if the
timing is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing
is more than 7 hours, the machine will not stop until reaches the setting time in sleep mode.
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart
module. In case of a sudden power failure, the module memorizes the setting conditions before the
power failure. The unit will resume the previous operation setting (not including Swing function)
automatically after 3 minutes when power returns.
If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes
and turn to auto mode as 24
℃
setting tem p.
If A/C is off before power off and A/C is required to start up now, the compressor will have 1 minutes
delay when power on. Other conditions, the compressor will have 3 minutes delay when restarts.
8.4.10 Vertical louver control function
Total four type operations for vertical louver control function: original orientation, orientation, vane
adjustment and horizontal swing.
8.4.10.1 Original orientation means when power on, the louver will turn to the datum mark. This action
has the highest priority. The other action of vertical louver can’t act until the original orientation action
Содержание 9V SERIES
Страница 1: ...9VSAP 1010 A SERVICE MANUAL MIDEA AIRCONDITIONER On Off SPLIT WALL MOUNTED TYPE 9V SERIES 9220 9221...
Страница 13: ...11 4 Refrigerant Cycle Diagram Cooling only Heat pump mode...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit Cooling only...
Страница 15: ...13 Cooling Heating...
Страница 16: ...14 5 2 Outdoor Unit Smaller than 18K model Cooling only...
Страница 17: ...15 Cooling Heating...
Страница 18: ...16 For 18 K model Cooling only...
Страница 19: ...17 Cooling Heating...