Page 6
NOTICE
The functional static pressure range of the air conditioner on site is 0-0.80 in-H2O
(0-200 Pa).
The data below represents the static pressures at full required air flow used for
AHRI testing.
NOTICE
The maximum functional total external static pressure can not exceed 0.80 in WC
or 200 Pa. The airflow reduces significantly beyond 0.80 in WC or 200 Pa.
System design should allow for the increased resistance of filters as they
become dirty.
Saf
ety
Pr
ecautions
Model
18-24K
30-36K
48-60K
Pressure
0.10 in-H2O (25 Pa)
0.15 in-H2O (37 Pa)
0.20 in-H2O (50 Pa)