IMPORTANT SAFETY INSTRUCTIONS 

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the 
unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS. 

CAUTION! 

The UPS must be connected to a grounded AC 

power outlet with fuse or circuit breaker protection. DO NOT 
plug the UPS into an outlet that is not grounded. If you need to 
power-drain this equipment, turn off and unplug the unit.

 

CAUTION! 

The battery can power hazardous components 

inside the unit, even when the AC input power is disconnected.

 

CAUTION! 

The UPS should be placed near the connected 

equipment and easily accessible. 

CAUTION! 

To prevent the risk of fire or electric shock, install in 

a temperature and humidity controlled indoor area, free of 
conductive contaminants. (Please see “Technical 
Specifications” on page 22 for acceptable temperature and 
humidity ranges).

 

CAUTION! (No User Serviceable Parts):

 Risk of electric 

shock, do not remove cover. No user serviceable parts inside. 
Refer servicing to qualified service personnel.

 

CAUTION! (Non-Isolated Battery Supply): 

Risk of electric 

shock, battery circuit is not isolated from AC power source; 
hazardous voltage may exist between battery terminals and 
ground. Test before touching.

 

CAUTION! 

To reduce the risk of fire, connect the UPS to a 

branch circuit with 15 amperes (UPS-OL1500R) / 20 amperes 
(UPS-OL2200R) / 30 amperes (UPS-OL3000R) maximum 
over-current protection in accordance with the National Electric 
Code, ANSI/NFPA 70.

 

CAUTION! 

The AC outlet where the UPS is connected should 

be close to the unit and easily accessible. 

CAUTION! 

Please use only UL-marked mains cable, (e.g. the 

mains cable of your equipment), to connect the UPS to the AC 
outlet.

 

CAUTION! 

Please use only UL-marked power cables to 

connect any equipment to the UPS. 

CAUTION! 

When installing the equipment, ensure that the sum 

of the leakage current of the UPS and the connected 
equipment does not exceed 3.5mA.

 

CAUTION!  

The UPS-OL1500R / UPS-OL2200R / 

UPS-OL3000R models may only be installed by qualified 
maintenance personnel.

 

CAUTION! 

Do not unplug the unit from AC Power during 

operation, as this will invalidate the protective ground 
insulation. 

CAUTION! 

To avoid electric shock, turn off and unplug the unit 

before installing the input/output power cord with a ground wire. 
Connect the ground wire prior to connecting the line wires! 

CAUTION! 

Do not use an improper size power cord as it may 

cause damage to your equipment and cause fire hazards. 

CAUTION! 

Wiring must be done by qualified personnel.

 

CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT 
EQUIPMENT!

  Under no circumstances this unit should be 

used for medical applications involving life support equipment 

and/or patient care.

 

CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS!

  To 

reduce the risk of fire, do not use with or near aquariums.  
Condensation from the aquarium can come in contact with 
metal electrical contacts and cause the machine to short out. 

CAUTION! 

Do not dispose of batteries in fire as the battery 

may explode. 

CAUTION! 

Do not open or mutilate the battery, released 

electrolyte is harmful to the skin and eyes. 

CAUTION! 

A battery can present a risk of electric shock and 

high short circuit current. The following precautions should be 
observed when working on batteries: 

1.  Remove watches, rings or other metal objects. 

2. Use tools with 

insulated 

handles. 

3.  Wear rubber gloves and boots. 

4.  Do not lay tools or metal parts on top of batteries. 

5. Disconnect charging source prior to connecting or 

disconnecting battery terminals. 

6. Determine if battery is inadvertently grounded. If 

inadvertently grounded, remove source from ground. 
Contact with any part of a grounded battery can result in 
electrical shock. The likelihood of such shock can be 
reduced if such grounds are removed during installation 
and maintenance. 

CAUTION! 

The unit has a dangerous amount of voltage. When 

the UPS indicators is on, the units may continue to supply 
power thus the unit’s outlets may have a dangerous amount of 
voltage even when it’s not plugged in to the wall outlet. 

CAUTION! 

Make sure everything is turned off and AC power is 

disconnected completely before conducting any maintenance, 
battery replacement, repairs or shipment. 

CAUTION! 

Connect the Protection Earth (PE) safety conductor 

before any other cables are connected. 

WARNING! (Fuses): 

To reduce the risk of fire, replace only 

with the same type and rating of fuse. 

DO NOT INSTALL THE UPS WHERE IT WOULD BE 
EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG 
HEAT SOURCE! 
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND 
THE HOUSING! 
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS 
HAIR DRYERS TO UPS OUTPUT SOCKETS! 
SERVICING OF BATTERIES SHOULD BE PERFORMED OR 
SUPERVISED BY PERSONNEL WITH KNOWLEDGE OF 
BATTERIES AND THEIR REQUIRED PRECAUTIONS. KEEP 
UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES! 
THE SOCKET-OUTLET SHALL BE INSTALLED NEAR THE 
EQUIPMENT AND SHALL BE EASILY ACCESSIBLE. 

Содержание UPS-OL1500R

Страница 1: ...before installing this product PRODUCT FEATURES Provides double conversion zero transfer time online backup protection Expansion battery packs for provisioning additional runtime needs Real time repo...

Страница 2: ...NG 7 HARDWARE INSTALLATION 8 Safety Precautions 8 Pr cautions de S curit 8 Rackmount Installation 8 Sliding Out the UPS From the Rackrail 10 INSTALLING YOUR UPS SYSTEM 11 System Block Diagram 11 Hardw...

Страница 3: ...S 18 Safety Precautions 18 Pr cautions de S curit 18 Remote Control 18 Wall Mounting Instructions 18 MAINTENANCE 19 Safety Precautions 19 Pr cautions de S curit 19 Storage 19 Replacement Batteries 19...

Страница 4: ...d wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards CAUTION Wiring must be done by qualified person...

Страница 5: ...ecter de la lignes ATTENTION Ne pas utiliser une taille incorrecte cordon car cela peut causer des dommages votre quipement et causer des risques d incendie ATTENTION Les travaux de c blage doit tre e...

Страница 6: ...n express ment approuv s par la partie responsable de la conformit pourraient annuler l autorit de l utilisateur utiliser l quipement NOTE This equipment has been tested and found to comply with the l...

Страница 7: ...unt Right Rail Left Hanging Bracket Right Hanging Bracket Rackmount Ears 2 Phone line USB communication cable Serial Interface Cable RS 232 Flat Head Screws M5x7L 8 Pan head screws M5x12L 4 Pan Head S...

Страница 8: ...sport en tenant fermement les deux c t s de l unit Ne pas soulever la batterie hors de la bo te de transport tout en maintenant la face avant de l appareil car cela pourrait causer des dommages ATTENT...

Страница 9: ...2L screws and 2 screws for both front and back and for each rail Tighten all screws 6 Slide hanging brackets on the UPS into the rails mounted in the rack with the front of the unit facing you Secure...

Страница 10: ...the Rackrail 1 Turn off and unplug the unit 2 The UPS is secured from being pulled out of the rack any further than its mid length by a safety lock mechanism Use both hands to hold the UPS and press t...

Страница 11: ...t unplug some equipment from the outlets first Make sure your equipment carries a load current within the unit s safe range See Technical Specifications on page 22 for more information 6 This UPS is e...

Страница 12: ...port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through this connection while the computer can monitor the UPS and alter...

Страница 13: ...ry Mode This state is enabled whenever utility power is disengaged Bypass Mode UPS is operating in Bypass Mode This state is enabled when the UPS detects an overload DC bus Bus Fault inverter High O P...

Страница 14: ...Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percent...

Страница 15: ...olumn of LCD screen 6 Press the and buttons to scroll through the different parameters 7 Press the ENTER button to select the parameter you want to change You may be prompted to save the selection if...

Страница 16: ...req 60Hz Converter OFF Sets the UPS converter to OFF 50Hz or 60Hz Screen Saver Disable 1 Minutes 5 Minutes 5 minutes When enabled sets the LCD screen saver to initiate after either 1 or 5 minutes of i...

Страница 17: ...LCD screen and the unit will perform a manual battery test Graphical Load Battery Capacity Display 1 Press the ESC button to return to UPS Status 2 Press the and buttons to scroll to the LOAD and BAT...

Страница 18: ...e Remote Control 1 Turn off and unplug the unit 2 Remove the multifunction LCD module by unscrewing the right panel separating it from the UPS and gently lifting the LCD module out Reinstall the right...

Страница 19: ...cha nes montres bracelets et bagues ATTENTION Ne pas ouvrir ni mutiler la batterie l lectrolyte lib r est nocif pour la peau et les yeux ATTENTION Pour viter un choc lectrique teindre et de d brancher...

Страница 20: ...out slowly and then put the new battery tray back into the compartment 5 Fasten back the connectors on the battery retaining cover Then insert the battery connectors and tighten the screws of battery...

Страница 21: ...e information about Middle Atlantic Product s Battery Replacement Program MAP UPS or EBPR Part Number Description Compatible Expansion Battery Packs UPS OLRBP 1 UPS OLRBP 2 UPS OLRBP 3 UPS OLRBP 4 UPS...

Страница 22: ...it Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 3 12V 9AH 6 12V 9AH Recharge Time Typically 5 hours for 0 100 Capacity 4 hours for 0 90 Cap...

Страница 23: ...ormation about Middle Atlantic Product s Battery Replacement Program EPO OFF Missing the EPO connection Check the EPO connection Wiring Fault Line and neutral wires are reversed Have a qualified elect...

Страница 24: ...OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THE MAXIMUM EXTENT PERMITTED BY APP...

Отзывы: