WARNING: When rein-

stalling the curved manifold
pipe, make sure the manifold
slide plate is positioned in its
holder and that the main spud is
inserted into the end of the noz-
zle, see Figures 6 and 7.

Reconnect union and replace back-
plate.

WARNING: Reposition the

combustion air shutter for the
maximum firing rate of the
selected spud capacity range.

Do

not change the Combination Valve
Gas Pressure Regulator setting at
this time.

CAUTION: The approximate

air and gas settings described above are for initial start-up only. Final settings must be
made in accordance with Section VIII, Initial StartUp/Adjustment 
Instructions for adjust-
ment of the manifold gas pressure are detailed in Section XI, Combination Gas Valve.

WARNING: Ignition is automatic. Make spark observations into combustion chamber

only with Main Manual Shut-Off Valve closed. Confirm that gas utilization equipment
does not contain any accumulated gases. Purge as described in Step 3 below.
1.

Check the burner piping and valves for gas leaks by applying a weak liquid soap solution to

unions and joints with the gas supply on. Leakage will be indicated by the appearance of soap
bubbles. Locate and correct all gas leaks before proceeding.

WARNING: DO NOT USE OPEN FLAME.

2.

Purging the air from the gas supply line at this step will expedite the first light-off.

CAUTION: Purge outside the building. Do not purge into the gas utilization equip-

ment.
3.

To purge the gas utilization equipment and chimney of any accumulated gases, turn Manual

Gas Cock Knob on the Combination Valve to 

OFF

, turn burner power on and set the operating

control to 

ON

or thermostat to call for heat. Let the blower run long enough to accomplish four

air changes, but not less than five minutes.

4.

CAUTION: Make sure that the capacity range of the installed spud and the prelimi-

nary combustion air shutter setting are suitable for capacity rating of the gas utilization
equipment. Refer to Section VII, Main Gas Spud 
and Table 3.
5.

RESET

the Electronic Control by setting the operating control to 

OFF

or the thermostat

below room temperature for at least 30 seconds, see Section XII, 

Electronic Control

.

6.

Confirm that Main Manual Shut-Off Valve is open. Turn Manual Gas Cock Knob on

Combination Valve to 

ON

.

7.

Turn operating control to 

ON 

or set thermostat above room temperature. Main flame should

come on when the motor reaches operating speed (after a 30 second prepurge in Canada).
Whenever the burner fails to light during the 6-second ignition trial, or if the flame is lost during
the burner run and not re-established within 6 seconds, the Electronic Control will shut off the
Combination Valve and 

LOCK OUT

. To 

RESET

the Control for restart, de-energize the Electronic

Control by setting the operating control to 

OFF

or thermostat below room temperature for at

least 30 seconds. If burner still fails to light, turn it off and repeat from Step 5 above. Then if nec-
essary, refer to the 

Trouble Chart

to isolate the problem.

WARNING: Repeated unsuccessful attempts to light will result in accumulated gases

in gas utilization equipment and chimney. To prevent these gases from reaching an
explosive level, periodically purge the gas utilization equipment and chimney as
described in Step 3.
8.

To make a preliminary setting of the burner input, determine the manifold gas pressure

required from Table 3 and adjust the Combination Valve pressure regulator accordingly, see
Section XI, 

Combination Gas Valve

.

9.

To determine the firing rate for NATURAL gas, accurately time 

test dial

for the number of

seconds for one revolution and use the following formula. All other gas utilization equipment
must be off.

Then divide by 1,000 for MBH value:

VIII Initial

StartUp/Adjustment

3600 x test dial size x BTU value

No. of seconds for one rev. test dial.

= BTU/Hr.

3600 x 1 x 1000

20

= 180,000 BTU/Hr. = 180 MBH

Example:

Table 3Main Gas Spud Capacity and 

Preliminary Gas and Air Settings

6

VII Main Gas Spud

Continued

Содержание Economite DS24A

Страница 1: ...ch hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions is not followed exactly a fi...

Страница 2: ...0 square inches of the total input rating of all gas utilization equipment in the confined space One grille should be located within 12 inches of the ceiling the other within 12 inches of the floor If...

Страница 3: ...zzle ribbon is free of for eign materials and also that the electrodes have not been damaged or displaced see Figure 7 WARNING The chimney shall be inspected for unsafe conditions such as deteriorat e...

Страница 4: ...e sure to hook up to a permanently live circuit Provide a fused on off disconnect switch carrying a minimum 3 amp fuse The frame of the burner must be well grounded A terminal is provided in the contr...

Страница 5: ...OPANE gas only and should be used only with the gas specified on rating plate A Standard Model DS24A Economite is shipped ready for NATURAL gas As shipped it is field convertible to PROPANE gas see Ta...

Страница 6: ...or capacity rating of the gas utilization equipment Refer to Section VII Main Gas Spud and Table 3 5 RESET the Electronic Control by setting the operating control to OFF or the thermostat below room t...

Страница 7: ...ng and shut off procedure refer to CONSUMER INSTRUCTIONS or to the instruction plate mounted on the burner DANGER Be sure that the Main Manual Shut Off Valve Combination Valve and Burner Power Switch...

Страница 8: ...stment an overfire condition could result when pressure returns to normal particularly if the regu lator adjustment screw is bottomed out ALWAYS confirm that at least the minimum rated gas pressure is...

Страница 9: ...OR REPAIR WARNING If PROPANE gas is used and the burner is located in a base ment crawl space or confining space contact your gas supplier about installing a GAS LEAK warning device PROPANE gas is hea...

Страница 10: ...ol b Between Electronic Control high voltage terminal and Spark Electrode Wire insert head of 8 x 3 4 or longer round head screw into snap terminal inside right angle rubber boot No spark broken wire...

Отзывы: