7.3.2 Technical details about the output
Note:
The analogue output of the BLE mA Link is a passive, not galvanically isolated current output.
Load voltage
12...24V
max. load (12V/24V, 24 mA)
360Ω/860Ω
I
out
4-20mA
I
out max
24mA (for error signalling)
Schematic diagram: Connection of an actuator
1
BLE mA Link
2
Actuator incl. power source for the current loop
(e.g. dosing pump controlled via analogue signal)