microSYST MS8111PWM3S Скачать руководство пользователя страница 6

3. TECHNICAL DATA 

Analog inputs

Linear current

0  ÷ 20 mA DC; 4  ÷ 20 mA  DC

Linear Voltage

0 ÷ 1 (10) V DC

Thermoresistor

Pt 100, P1000 

EN 60751

Thermocouple

J, K,

EN 60584

Other

By order

Measurement accuracy

 0.15% of the range

Digital inputs

Start / Stop timer

Optically isolated- active level GND ISO, 

for NPN sensor

Discrete outputs

    
K1 - ON/OFF or PWM
К2 - ON/OFF or PWM
К3 - Function

Options:
Relay 250 V / 5,10 A
Triac 250 V / 2 A
NPN OC uniso Ucemax=65V ,Icemax=100 mA 
NPN OC iso  Ucemax=80V ,Icemax=1A 

Function К3

- Alarm
- Timer

Analog outputs, (optional )

optically isolated

АО1 – current or voltage
АО2 – current or voltage

0  ÷ 20 mA DC; 4  ÷ 20 mA

0 ÷ 1 (10) V DC

Power supplying a transmitter

(11.5 ÷ 14.5) V DC   150 mA    unstabilized

Indication and keyboard

Display

2 x 4 digits LED 10 mm

Display range

-1999 … 9999

Display format

X.XXX    X X.XX   XXX.X    XXXX

Keyboard

semi-sensor

Power supply

Supply voltage ; frequency

230VАС / max 20mA; 50 Hz

Other

Depending on order code

Operating conditions

Temperature and relative 

humidity without condensation

Operating:  -10 ÷ 70 °C / 10 ÷ 85 % rh
Storage : -20 ÷ 70 °C / 10 ÷ 90 % rh

Dimentions

Overall dimensions (WxHxL)

96 x 48 x 128 mm 

Installation

in hole 90 x 44 mm

Weight

max 300 g

Protection class

IP40

Редакция документ 2018-11-02

    6

Содержание MS8111PWM3S

Страница 1: ...COMPETENCE IN MEASUREMENT UNIVERSAL DUAL CHANNEL PROGRAMMABLE CONTROLLER WITH TIMER OR ALARM MS8111PWM3S v1 2 USER MANUAL PLOVDIV 2018 2018 11 02 1...

Страница 2: ...2018 11 02 2...

Страница 3: ...s section Analog outputs are retransmitting input variables Timer has 2 main modes as an independent from input variables In this mode the timer is started by front depending on whether the measured p...

Страница 4: ...ION AGAINST EMI Electromagnetic Interference 13 12 HIDDEN SYSTEM PARAMETERS 14 Controls two processes simultaneously by proportional or ON OFF mode Programmable timer or alarm Analog outputs Display 2...

Страница 5: ...ge Code PA PF PB 230 VAC 24 VAC 24 VDC 12 VDC 24 VDC other 50Hz 30 isolated 30 isolated 15 unisolated 15 unisolated PC PD PX Code D N S Alarm Timer not connected Decimal point upper and lower limit of...

Страница 6: ...Alarm Timer Analog outputs optional optically isolated 1 current or voltage 2 current or voltage 0 20 mA DC 4 20 mA 0 1 10 V DC Power supplying a transmitter 11 5 14 5 V DC 150 mA unstabilized Indicat...

Страница 7: ...ime expires the entry into the mode does not take place In programming mode the lower display displays the parameter name and the upper display its value Editing the values is done with the DOWN and U...

Страница 8: ...active until pressing the external button or by a power failure MODE 2 The timer starts depending on whether the measured value PV has reached the controller SP setting The Start timer input must hav...

Страница 9: ...the set time by pressing and holding the SET and UP buttons in the indicated sequence for more than 5 seconds until SP t shows on the lower display Editing the value is done vie the DOWN and UP button...

Страница 10: ...ne because it compensates the measurement error of the temperature due to the additional resistance introduced by the connecting wires Connecting three wire sensors to the controller is done according...

Страница 11: ...unit Fig 4 The device provides unstable voltage from 11 5V to 14 5V max 50mA 6 3 2 Transmitter with own power supply Fig 5 6 3 3 Three wire transmitter powered by the device Fig 6 The device provides...

Страница 12: ...l switch start by level Used when the timer operates depending of the measured input variables 8 OUTPUTS CONNECTIONS Depending on the option of executing the corresponding digital output in the order...

Страница 13: ...ality for Channel 1 Within the range of change of the input parameter t 2 Channel 2 period 0 128 seconds When the value is zero the regulation becomes positional with parameter Zon2 assuming the role...

Страница 14: ...nterference Recommendations for use of connecting wires Wires that carry a similar type of signals can be packed together but if the signals are different the wires must be separated to prevent electr...

Страница 15: ...hannel 1 0 128 seconds JP 1 Filter rebound threshold of Channel 1 0 255 units of input When changing the input variable to a value greater than the preset and maintaining the new state for a time grea...

Страница 16: ...0 start at PV1 SP1 PV2 SP2 48 start at PV1 SP1 PV2 SP2 56 start at PV1 SP1 PV2 SP2 64 start at PV1 SP1 or PV2 SP2 72 start at PV1 SP1 or PV2 SP2 80 start at PV1 SP1 or PV2 SP2 88 start at PV1 SP1 or P...

Страница 17: ...transport bad conservation wrong exploitation naturedisasters not following the instructions and the cases when there is an attempt to fix anydefects by other people In those cases the issue is being...

Отзывы: