7.3.
System parameter setting
Parameters accessible at pressed button
at switch on of the power supply.
The System Parameters apear after basic parameters.
Access is possible by holding the button
up to power supply turn off
Change with extreme caution, because their change can result in incorrect
operation of the appliance!
Changing the P1 and P0 required standard device connected to the output.
SYSTEM PARAMETERS
Parameter
Description
Value
Factory
value
P1
Multiply coefficient for analog output
-1999 ÷ 9999
P0
Offset for analog output
dPnt
Decimal point
128 –
х.ххх
64 –
хх.хх
; 32 –
ххх.х
;
0 – хххх
A db
Zone of operation of the filter
FiLt
0 ÷ 255
**
10%
of the
range
Adbt
Waiting time after leaving the zone filter to adopt
the new value.
0 ÷ 255 х 0.5 s
4
dSPL
Consistently lower and upper limits of change of
the displayed parameter.
When change is automatically recalculated
settings display input value corresponding to
the input and output signals.
-1999 ÷ 9999
**
End
Exit after last parameter
**
Dimension and decimal point according to the measured value.
Input and output signals
are factory set
according to the order code. To change the
format of the displayed parameter is enough to change only
dSPL
and
dPnt
.
Recalibration of the Process Variable is possible only if the controller is factory set for
analog input signal.
There is an option in production programmable linearization for a specific sensor, in
which case the change affects only the range of the analog output.
Document revision 2015-03-16
9