1.
DESIGNATION
MS8104k5
and
MS8104k3
are designed for process control in ON / OFF control mode. The
difference between the two controllers is only in the number of discrete outputs - 5 for MS8104k5
and 3 MS8104k3.
One of discrete outputs is alarm with switch-on delay and the rest are ON / OFF controlled
with programmable hysteresis All outputs have independent set points, and user selectable positive
or negative logic of control / type "heating" or "cooling" /.
The large number of digital outputs with independent set points, provide the opportunity
controllers to be used for stage control. Stage control allows to switch on and off heavy loads at
different times to protect the power supply network of shock loads.
Parameters hysteresis, alarm levels and others are user programmable.
The controller has an analog output, which transmit the input value in unified output current
or voltage signal.
The range of the displayed parameter is user adjustable only when the input
parameter is a linear / as unified current or voltage signal /.
Sets up the known values of the input signal by a reference / signal calibrator / or
direct signal from the transmitter corresponding to the lower and upper level of
the site / As a reservoir, a current transformer, etc. /