4.1 Control Board (intern)
Boot Jumper:
This Jumper must not be set within normal operation.
If the display does not work according to the rules, f.e. after a faulty
software- or configuration download, the following steps should be
executed:
Power off the display.
Set the boot jumper.
Power on the display.
Use the micon software to load the configuration resp. the application
software into the display again (see corresponding chapter).
After a successful download, power off the display.
Remove the boot jumper.
Power on the display.
Boot Jumper