Control board O047+T047idro
Micronova
page 35 of 113
ENG
OPERA
TING M
ODE
figure 18
Adjusting the water temperature set
T
o change the water temp set press P1, then to increase press P1 or P2 to decrease. To
exit and confirm set press P4.
figure18
figure 19
Modulation status
The modulation status with active
“
RISC
”
mode occurs when certain conditions are
satisfied. The stove goes to power 1 and on the display, the message in
figure 19 is
shown.
The room temperature
“
air
”
alternates with water temperature and power stove
set.
The conditions are shown below. It only takes one satisfied condition to switch to the
modulation state:
•
Room temperature probe = or > Room temperature set :
The stove goes in modulation when the room temperature set is reached, indepen-
dently from the fact that the water set is satisfied
•
Water probe = or > Water set:
The stove goes in modulation when the water set is reached, independently from the
room temperature set or T
-
E contact is open. If the room set is set in H2O, the stove
only goes in modulation when the water set is reached.
•
T
-
E contact open ( room temperature set on T
-
E):
When the contact of the external thermostat T
-
E is open, the stove goes into modula-
tion, independently from the fact that the water set is satisfied.