OPERATING MODE
The operating mode changes according to the type of system used (settable via parameter
M
-
9
-
2
-
15), however, the entire ignition, start, work, brazier and extinguishing phase is
COMMON
. Following, the normal operation of the controller installed in a hydro stove,
will be described. We will, then, focus on the work and standby phase according to the type
of system set
figure 6
figure 7
7.1 Starting the stove
To switch on the stove, press P4 for a few seconds. The ignition is signaled in the di-
splay with the word "Start" as shown in
figure 7
.
The glow plug and the fumes extractor light up in the status box. This phase lasts for a
time given by the M
-
9
-
4
-
33 parameter, the fumes extractor speed is given by the M
-
9
-
4
-
35 parameter.
In this phase, a timer given by the M
-
9
-
4
-
01 parameter is loaded, within which the sto-
ve must light up. If the stove doesn
’
t switch by the end of the expired time, it goes into
alarm state with the corresponding message on the display. (refer to chapter 9)