JADE Setting: Under the “System Setup” menu, set AUX1-OUT to
“SYS” which will close JADE relay on fault detection
Examples of annunciator lights
would include these Grainger lights:
- Item #20C841
- Item #20C846
*Light solution cannot exceed 1.5A steady state @ 30VAC and
7.5A inrush at 30VAC
AUC2-1
OCC
E-GND
EXH1
AUX1-0
Y21
Y2O
Y1I
Y1O
C
IAQ COM
IAQ (2-10V)
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
MAT
OAT
OAT
To
“C” T
erminal
To
“AUX1-0” T
erminal
Annunciator Light*
REMOTE (DOWNSTAIRS) MONITORING OF
CONTROLLER’S FAULT DETECTION AND
DIAGNOSTICS
Many codes including IECC, Title 24, and ASHRAE 90.1 require
that the economizer’s faults be accessible by operating or service
personal, or annunciated locally on zone thermostat. To setup
remote monitoring on the controller, under SYSTEM SETUP,
AUX1-OUT must be set to SYS.
The latest versions of Honeywell’s TH8321WF or TH8321R
thermostats are options for meeting this requirement. Figure 33
shows an example of the thermostat wiring to the Jade controller.
Follow instructions provided with Honeywell thermostat.
Figure 33 – Thermostat Wired For Remote FDD
W7220 Economizer Controller Module
Another option that is acceptable to some codes is an annunciator
light visible by service personnel. See Figure 34 for typical wiring
to the Jade controller. Refer to codes for proper labeling of light.
Figure 34 – Annunciator Light Wired for Remote FDD