Figure 27 - Use Part of 9962-0407-SAOEXT Harness for MAT Sensor on LC Units

Step LC4.

 The connectors on the right side of Figure 25 on 

the 48LCHSRADH—A00 harness attach to the Jade W7220 

controller installed in the unit control box. See Figures 25 and 28. 

48LCHSRADH—A00 harness connectors are labeled to easily 

identify the plug-in location on the controller. 

Step LC5.

 Locate the Compressor Staging Control (CSC) board 

in the HVAC unit. When a field-installed economizer is used the J5 

jumper on the CSC must be removed. Remove the J5 jumper. See 

Figure 28

Step LC6.

 The connectors on the left side of Figure 25 on the 

48LCHSRADH—A00 harness attach to the unit’s CSC board. 

Connect J3 and J5 plugs to the CSC board.

Step LC7.

 Screw the green wire with yellow stripe in the 

48LCHSRADH—A00 harness to the control box (ground). See 

Figures 12 and 28.

Step LC8.

 Mount the provided 9901-2021 mixed air temperature 

(MAT) sensor (C7250) to the indoor blower. Confirm that the screws 

do not interfere with blower rotation. See Figure 15.

IMPORTANT: 

The brown and orange wires in the indoor blower section for the 

mixed air sensor have spade terminals, and will not connect directly 

to the MAT sensor, which requires a 2-pin plug.

Some Economizer Models: 

Locate brown and orange MAT wires on the 9962-0407-SAOEXT 

harness, see Figure 15. Cut the orange and brown leading to the 

2-pin MAT plug. Splice these 2 wires to the brown and orange wires 

in the indoor blower section. Connect the 2-pin plug to the mixed air 

sensor, see Figures 27 and 28.

Other Economizer Models:

Locate the brown and orange wire on the original Jade harness, 

see Figure 27. Disconnect the terminals on the brown and orange 

MAT wires, see Figure 27. Connect these terminals to the brown 

and orange wires factory installed in the blower section. Connect 

the 2-pin plug to the mixed air sensor, see Figure 28.

Step LC9.

 Follow steps 21 through 25 earlier in instructions.

Instructions for 48/50LC 07-12 Units Only

Important: This page is for economizer installation instructions on 48/50LC 07-12 units only.

2-Pin Plug

to MAT

BRN

ORG

BRN

ORG

Disconnect Terminals

or Cut and Splice

Use This Section

on LC Units for

Mixed Air Sensor

Содержание ECD-SRTCA-D2

Страница 1: ...Foremost HVAC Accessory Manufacturer Economizer ECD SRTCA D2 Install Guide...

Страница 2: ...Table of Contents Topic Page Number General 1 Topic Page Number General Install Instructions 1...

Страница 3: ...ating the compressors when the outdoor air is too humid integrating the compressor with outdoor air when free cooling is available and locking out the compressor when outdoor air temperature is too co...

Страница 4: ...581J 551J 04 06 549J 547J 559J 582J 04 06 548J 580J 558J 04 07 Dry Bulb OA Sensor ECD SRT12CA D2DH Enthalpy OA Sensor ECD SRT12CA D2EH Large Cabinet 581J 551J 07 12 580J 558J 08 14 548J 08 12 549J 07...

Страница 5: ...California Energy Commission Title 24 prescriptive section 140 4 damper leakage etc and mandatory section 120 2 i for Fault Detection and Diagnostic controls Economizers meet ASHRAE 90 1 damper leaka...

Страница 6: ...t wiring harness See Figure 5 Note the 12 pin jumper plug should be saved for future use in the event that the economizer is ever removed The jumper plug is not needed as long as the economizer is ins...

Страница 7: ...ect 10 Pin Jade Plug to Central Terminal Board Figure 11 Connect Red and Brown Wires to Central Terminal Board Step 14 Connect the White wire from the Jade controller harness to the W1 terminal on the...

Страница 8: ...he divider between the control box and the indoor blower section See Figure 14 Important See note below Figure 14 Route 9962 0407 SAOEXT Harness to Indoor Blower Section See note below Some control bo...

Страница 9: ...rness See note For 48 50LC 07 12 Instructions see pages 10 12 Figure 17 Economizer Hood Assembly ECONOMIZER P N A B C D SHIP WT ECD SRT12CA D2 H 30 37 17 43 19 05 29 5 55 lb ECD SRT34CA D2 H 40 37 22...

Страница 10: ...unit control box panel See Figure 6 Economizer performance charts are below See base unit installation manual to make adjustments to meet building ventilation requirements Economizer Hood Filter Door...

Страница 11: ...W7220 JADE Controller Field Mounted in Unit Control Box MAT MAT OAT OAT ACT 24V ACT COM S BUS S BUS EXH1 IAQ COM ACT 2 10 AUX1 OUT IAQ 2 10 E GRD AUX2 IN Y1 IN Y1 OUT Y2 OUT Y2 IN OCC C R 10 Pin Femal...

Страница 12: ...0LC 07 12 units only Figure 24 Remove Complete Harness Factory Attached to W7220 Controller Figure 24A 9962 0407 SAOEXT Not Used on 48 50LC 07 12 Units Note The complete 4 wire 9962 0407 SAOEXT harnes...

Страница 13: ...indoor blower Confirm that the screws do not interfere with blower rotation See Figure 15 IMPORTANT The brown and orange wires in the indoor blower section for the mixed air sensor have spade terminal...

Страница 14: ...trol box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220 controller from the Carrier factory is removed and not...

Страница 15: ...2 sensor for outside air sensor the dipswitches on the sensor must be set to OFF OFF OFF See Table 8 The 2 gray wires with a plug from the economizer harness in the return chamber plug directly into t...

Страница 16: ...ness Provided in 9901 2022 DIFF JC2 Kit DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZER OFF WHEN DESCRIPTION FIXED DRY BULB 1 3 5 11 16 OAT exceeds 75 F 2 4 10 OAT exceeds 73 F 6 8 9 OAT exce...

Страница 17: ...90 1 require that the economizer s faults be accessible by operating or service personal or annunciated locally on zone thermostat To setup remote monitoring on the controller under SYSTEM SETUP AUX1...

Страница 18: ...nical units is the Honeywell W7220 which is to be located in the RTU base unit s Control Box See Fig 35 for button description of the W7220 controller The W7220 controller provide the following 2 line...

Страница 19: ...UT MIN POS The minimum position allows for ventilation even when not in the free cooling mode If you have a single speed unit there will be only one minimum position setting The default is 2 8 volts b...

Страница 20: ...sensor is connected and displays measured discharge temperature Displays if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMP...

Страница 21: ...ected Setpoint for Demand Control Ventilation of space Above the setpoint the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint MIN POS 2 8 V 2 t...

Страница 22: ...3000 ppm Increment by 50 CO2 ppm span to match CO2 sensor STG3 DLY 2 0h 0 min 5 min 15 min then 15 min intervals Up to 4 h or OFF COOLING STAGE 3 DELAY Delay after stage 2 for cool has been active Tu...

Страница 23: ...0 terminal provides 24 Vac out ACT UNDER V n a n a ACTUATOR VOLTAGE LOW Voltage received at actuator is below expected range ACT OVER V n a n a ACTUATOR VOLTAGE HIGH Voltage received at actuator is ab...

Страница 24: ...c Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source ACT 2 10 2 10 Vdc Damper Actuator Output 2 10 Vdc ACT COM COM Damper Act...

Страница 25: ...command dry bulb outdoor enthalpy differential dry bulb or differential enthalpy a call for cooling Y1 closes at the thermostat will cause the economizer control to modulate the dampers open and close...

Страница 26: ...to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always illuminated What is a good setpoint for the Mixed Air Tempera ture MA...

Отзывы: