MANUAL MODE 

WARNINGS: 

- Changeover parameters like delays and filters are disabled. 

- No errors are detected or signalled. 

“SETTINGS”

 menu available. 

CHANGEOVER MAINS/GENSET: 

With Mains as source press key 

 

(RUN)

 to start the Genset, once started it will send to the device the OK for a 

correct ignition as indicated in the top right corner by the 

 rotary symbol. 

Note:

 If the Genset will fail to start, an alarm signal will be generated and the symbol will be 

.

 

It is highly recommended to wait for the voltage and frequency values to be corrected an stable before to 
activate the changeover. 

To activate the changeover press together for 

1s

 the keys 

 and 

 

(GENSET)

At the prompt 

“Perform switchover?”

 press key 

 

(YES)

 to confirm or 

 

(NO)

 to cancel. 

The changeover is confirmed by the Genset image, from the contact symbol closed   (wich confirms the contactor 
bobbin activation 

LG

) and from the voltage and frequency background colour changed. 

 

Therefore to switch from Genset to Mains press together for 

1s

 the keys 

 and 

 

(MAINS)

, finally press the 

key 

 

(STOP)

 to switch-off the Genset. 

 

!!! WARNING !!! 

In manualemode no controls or warning are generated so, to avoid troubles, operate carefully. 

 

 

AUTO MODE 

WARNINGS: 

- All the processes and functions are uniquely handled by the device. 

“SETTINGS”

 menu available.

 

- It is not possible to switch-on  or off the Genset, the key 

 

(RUN/STOP) 

is disabled. 

- Measurements follow the system status and phases are monitored individually. 

- In source Mains, the missing of one single phase triggers the changeover procedure. 

- In source Genset, the missing of one single phase trigger the error 

“Er1”

- Frequency control is active only in Genset source mode. 

In three phase systems also the asymmetry check is active 

(only model DTS-E)

 

Содержание EVO DTS-B

Страница 1: ...i de ntre inere asupra dispozitivului ndep rta i toate tensiunile de la intr rile de m surare i de alimentare i scurtcircuita i bornele de intrare CT Produc torul nu poate fi considerat responsabil pe...

Страница 2: ...microidea it Web www microidea it TYPICAL WIRING DIAGRAM for reference purposes only The installation has to be equipped with an external disconnection device that should be easily reachable and iden...

Страница 3: ...ternatively from Auto and Mode Using the P13 Working mode default MAN we can define the default mode we can also lock this working mode by using the P14 Working mode lock default OFF The transition fr...

Страница 4: ...repeat the sequence if you need to modify others To exit this menu press for 3s the key EXIT 6 You will be prompted for Save parameters then press key YES or NO 1 2 3 4 5 6 FACTORY RESET default para...

Страница 5: ...10 Genset Mains delay s 1 240 Delay between stable Mains and Genset changeover 10 P11 Genset off delay s 1 240 Delay time between changeover and Genset switch off 30 P12 Frequency tolerance Hz 1 9 Fre...

Страница 6: ...firm or NO to cancel The changeover is confirmed by the Genset image from the contact symbol closed wich confirms the contactor bobbin activation LG and from the voltage and frequency background colou...

Страница 7: ...ON contact closed Relay ALARM ON contact closed ERRORS P18 Genset Mains forced default OFF If disabled every time an error occurs the Genset will be switch off and the device will remain on Genset sou...

Страница 8: ...filter default 1s the display will show Er4 Phase asymmetry of the Genset beyond limits set in P20 PH asymmetry tolerance default 20V Missing Voltage Error or Contactor malfunction only DTS E model Th...

Страница 9: ...ET 2 Press key to set the value to ON then press SET to confirm and access the PASSWORD screen where you will be asked to insert the actual password if this is the first time leave the value default 0...

Страница 10: ...ntactor coil 5A 250V TG Genset contactor coil 5A 250V Alarm Relay Output Max current 8A Max voltage 250V Electrical contact Life 100 x 103 ops Mechanical contact Life 30 x 103 ops Ambient conditions O...

Страница 11: ...11 12 ITALY Tel 39 035 773 925 Fax 39 035 773 e mail microidea microidea it Web www microidea it BACK PANEL CONNECTIONS DIMENSIONS Only for DTS E model...

Страница 12: ...12 12 ITALY Tel 39 035 773 925 Fax 39 035 773 e mail microidea microidea it Web www microidea it...

Отзывы: