SETTINGS
To
access the menu:
1) Press for
5s
key
(SET)
to access
“SETTINGS”
..
2) Use keys
and
to scroll trough the parameters to modify.
3) Press key
(SET)
to select the desired value.
4) Use keys
and
to modify the selected value (keep the key pressed if you need to increase the speed of
the value modification).
5) Press key
(SET)
to go back to the parameters, then repeat the sequence if you need to modify others.
To exit this menu press for
3s
the key
(EXIT)
.
6) You will be prompted for
“Save parameters?”
then press key
(YES)
or
(NO)
.
1)
2)
3)
4)
5)
6)
FACTORY RESET (default parameters)
- Press for
5s
key
(SET)
to access
“SETTINGS”
.
- Press together the keys
and
(SET)
for
3s
.
- At the prompt
“Default parameters?”
press key
(YES)
to confirm or
(NO)
to cancel the procedure.
- You return to the
"SETTINGS"
, to exit this menu press for
3s
the key
(EXIT)
.
- At the prompt
“Save parameters?”
press key
(YES)
to confirm or
(NO)
.
IMPORTANT:
only after this last confirmation the instrument will consider and use all the changes previously
done into the SETTINGS menu.