MC3V-X/10-4
Doc. N°
MO-0355-ING
Microe
ner
- Copyright 20
11
FW
940.09.01.x
Date
06
.0
1
.20
11
Rev.
4
Pag.
25
of
32
11.6 - RelayCfg
(Relay Configuration)
To associate one of the Output Relays to one or more functions (see § Password): enter the menu
“R/W Set”, select “Relay Cfg”, select the “Relay #” to be programmed, select “Link”; at this stage the list
of the available functions is displayed. Scrolling the list by the “+” and “-“ keys the function is selected
and than assigned by the key “Enter”. The assignation is confirmed by the function indication that
switches from blinking to steady.
Any of the Output Relays can be programmed to work in two different modes:
N.D.
Normally Deenergized Relay is energized on trip of the associated functions
N.E.
Normally Energized
Relay is deenergized on trip of the associated functions
Programming of working mode is made as above selecting “OpMode” instead of “Link”.
Display
Relay
Type
Default
Value
Description
Setting Range
Step
Link
→
tV>, tV>>, tf>,
tVo>, fV2>
Association of functions to
output relay R1
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
Relay1
(R1)
OpMode
→
N.D.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-
Link
→
tV<, tV<<, tf<,
tV1<
Association of functions to
output relay R2
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
Relay2
(R2)
OpMode
→
N.D.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-
Link
→
V>, V>>, V<,
V<<, Vo>
Association of functions to
output relay R3
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
Relay3
(R3)
OpMode
→
N.D.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-
(UX10-4) Additional Expansion Module (10 Digital Input – 4 Output Relay)
By the interface program “MSCom 2” it is possible to Activate/Deactivate the modules.
Display
Relay
Type
Default
Value
Description
Setting Range
Step
Link
→
-
Association of functions to
output relay 1.R1
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
1.R1
OpMode
→
N.D.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-
Link
→
-
Association of functions to
output relay 1.R2
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
1.R2
OpMode
→
N.D.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-
Link
→
-
Association of functions to
output relay 1.R3
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
1.R3
OpMode
→
N.D.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-
Link
→
-
Association of functions to
output relay 1.R4
V> - tV> - V>> - tV>> - V< - tV< - V<< - tV<< - f> - tf> - f< -
tf< - Vo> - tVo> - V1< - tV1< - V2> - tV2> - RTD - IRF -
HwRecov. 1.D1, 1.D2, 1.D3, 1.D4, 1.D5, 1.D6, 1.D7, 1.D8,
1.D9, 1.D10, Canstatus.
-
1.R4
OpMode
→
N.E.
N.D. (Normally Deenergized)
N.E. (Normally Energized)
N.D./N.E.
-