MC20-X/10-4
Doc. N°
MO-0352-ING
Microener - Copyright 2010
FW
720.07.01
Date
09.04.2008
Rev.
1
Pag.
13
of
35
2.2.5.7 -
IoH (3F51N)
- Third Earth Fault protection level
FuncEnab
Enable
[Disable / Enable]
Options
BI
Disable
[Disable / Enable]
Trg
Enable
[Disable / Enable]
TripLev
IoH
2.00
Ion
(0.01
9.99)
step 0.01 Ion
Timers
tIoH
0.10
s
(0.05
60.00)
step
0.01 s
FuncEnab
: If disable the function is disactivated
BI
: Operation controlled by Blocking Digital Input
Trg
: Function operation triggers the oscillographic wave form capture
(see § 2.2.3.12)
IoH
: Minimum Zero Sequence Residual Current Pick-up level
tIoH
: Trip time delay
2.2.5.8 -
BF (F51BF)
- Breaker Failure
FuncEnab
Enable
[Disable / Enable]
Options
TrR
Relay1
Relay1 – Relay2 – Relay3 – Relay4
TripLev
No Param
No Parameters
Timers
tBF
0.20
s
(0.05
0.75)
step
0.01 s
FuncEnab
: If disable the function is disactivated
TrR
: Output relay programmed for trip command to the Circuit Breaker
tBF
: Trip time delay
Operation: If after the time “tBF” from pick-up of the programmed relay “TrR” the current
measured still exceeds 5%In, the output relay associated to the “BF” function is operated
(relay another than TrR).
2.2.5.9 -
RTD
- Remote Trip
Remote trip is controlled via the Digital Input D2.
FuncEnab
Disable
[Disable / Enable]
Options
No Param
No Parameters
TripLev
No Param
No Parameters
Timers
No Param
No Parameters
FuncEnab
: If disable the function is disactivated