4. SIGNALIZATIONS
Eight signal leds (normally off) are provided:
a)
Red LED
IL
(OVERLOAD)
Flashing when measured current exceeds the set pick-up IL.
Illuminated on trip after expiry of the set trip time delay tIL.
b)
Red LED
IH
(PHASE FAULT)
Same as above related to IH and tIH.
c)
Red LED
OL/OH
(EARTH FAULT)
Flashing when Earth Fault current exceeds the pick-up level OL or OH.
Illuminated on trip of the time delayed element tOL or tOH.
d) Red LED
UL/UH
(UNBALANCE)
Flashing when the UNBALANCE voltage exceeds the pick-up level UL or UH
Illuminated on trip of the time delayed element tUL or tUH.
e) Yellow LED
PROG/IRF
Flashing during the programming of the parameters
Lit-on in case of Internal Relay Fault.
f) Red LED
I
(RECLOSE
INHIBIT)
Flashing when the current drops below the set level I
.
Illuminated on trip after expiry of the set trip time delay tI
; the led
automatically extinguishes at the end of the set wait time for enabling to
reenergize the capacitor bank.
g) Red LED
BR. FAIL.
Flashing during the reclose inhibition time tRI
Lit-on when the BREAKER FAILURE function is activated.
h) Yellow LED
B.I./F.D.
(FUNCTION
DISABLED)
Illuminated when the operation of one or more of the relay functions has
been disactivated in the programming
Flashing when a block signal is present.
The reset of the leds takes place as follows
Leds
a,b,c,d,g
From flashing to off, automatically when the lit-on cause disappears
From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
Leds
e,f,h
From ON to OFF, automatically when the lit-on cause disappears.
In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power
supply is restored.