IM30-CV
Doc. N° MO-0150-ING
Rev.
1
Date
14.07.2003
Copyright 2010 - Microener
Firmware:
1.0X
Pag
13
di
24
Display
Description
Setting Range
Step
Unit
F(OL)
D
Operation characteristic of the low-set earth fault element
D = Independent definite time
SI = Dependent normal inverse time
D
SI
D
SI
-
OL
0.1
In
Trip level of low-set earth fault element
(p.u. of the rated current of the phase C.Ts.)
0.1 - 1.0 - Dis
0.01
In
tOL
0.05
s
Trip time delay of low-set earth fault element
In the inverse time operation it is the trip time delay
at Io = 5xOL
0.05
– 30
(1-9.99)
0.01
(10-30) 0.1
s
OH
0.2
In
Trip level of high-set earth fault element
(p.u. of the rated current of the phase C.Ts.)
0.1 - 2.0 - Dis
0.01
In
tOH
0.05
s
Trip time delay of the high-set earth fault element
0.05
– 9.99
0.01
s
F(UL)
D
Operation characteristic of the low-set unbalance element
D = Independent definite time
SI = Dependent normal inverse time
D
SI
D
SI
-
UL
0.02
Un
Trip level of low-set unbalance element (p.u. of the rated
voltage of the P.Ts. for unbalance detection)
0.02 - 0.8 -Dis
0.01
Un
tUL
1.0
s
Trip time delay of low-set unbalance element
In the inverse time operation it is the trip time delay
at Io = 5xOL
1.0 - 30
(1-9.99)
0.01
(10-30) 0.1
s
UH
0.04
Un
Trip level of high-set unbalance element (p.u. of the rated
voltage of the P.Ts. for unbalance detection)
0.01 - 1.0 - Dis
0.01
Un
tUH
1
s
Trip time delay of the high-set unbalance element
0.1 - 300
(1-99.9) 0.1
-
(100-300) 1
s
I<
0.1
In
Trip level of undercurrent element
(p.u. of the rated current of the phase C.Ts)
Dis - 0.10 - 1.0
0.01
See note 1
In
tI<
1
s
Trip time delay of the undercurrent element
1.0 - 99.9
0.1
s
tRI<
5
m
Wait time for the reenergization of the capacitors
Dis - 0.5 - 100
0.1
m
Uc
0.00
Un
Unbalance compensation level
0.00 - 0.2
0.01
See note 2
Un
c
0
°
Uo
IA phase displacement (counter clockwise rotation)
0 - 359
1
°
B14
Dis
C/B status monitoring input enabled/disabled
En - Dis
-
-
tBF
0.1
s
Max reset time delay of the instantaneous element after
tripping of the delayed element
0.1-0.75
0.1
s
NodAd
1
Identification number for the connection on serial
communication bus
1 - 250
1
-
The setting Dis indicates that the function is disactivated.