2.2 - Operation and Algorithms
2.2.1 - Reference Input Values
Display
Description
Setting Range
Step
Unit
I1
100
A
Rated Primary current of phase C.T.
1 -
9999
1
A
I2
5
A
Rated Secondary current of phase C.T.
1 -
5
1/5
A
In
100
A
Reference primary current of the relay
1 -
9999
1
A
Freq
50
Hz
System rated frequency
50 -
60
10
Hz
TW
30
min
Warming-up time constant for Thermal Image
1 -
60
1
min.
Ib
105
%In
Max. admissible continuous overload for Thermal Image
50 -
130
1
%In
2.2.2 - Input quantities
2.2.2.1 - Mains Frequency (Freq)
The relay can operate either in 50Hz or 60Hz systems.
The rated Mains
Frequency “
Freq
”
must be set accordingly.
2.2.2.2 - Phase Current inputs (I1)
The relay directly displays the r.m.s. value of the Phase Currents “
IA
”, “
IB
”, “
IC
” flowing in the Primary
of the input Current Transformers and refers all its measurements to that value.
To make the relay properly working with any C.T., when programming the relay settings, input the value
“
I1
”
of the primary current of the phase C.Ts
2.2.2.3 - Earth Fault Current Input (Ion)
Same as for the Phase Currents, the relay directly displays the r.m.s. value of the Zero Sequence
Residual Current flowing at the Primary of the Current Transformers.