MC30-R2
Doc. N°
MO-0462-ING
Copyright 2012
FW: 1290.37.01.x
Date
06.09.2022
Rev.
1
Pag.
13
of
38
3.3 - I>> (2F51) - Second overcurrent protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
2xI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
→
Sh1
No
[No / Yes]
→
Sh2
No
[No / Yes]
→
Sh3
No
[No / Yes]
→
Sh4
No
[No / Yes]
TripLev
→
I>>
0.05
In
(0.50
40.00)
step 0.01
In
Timers
→
tI>>
0.05
s
(0.05
60.00)
step
0.01
s
→
t2xI
0.02
s
(0.02
9.99)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is disactivated
BI
: Operation controlled by Blocking Digital Input
2xI
: Automatic threshold doubling on inrush
Trg
: Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
Sh1
: Tripping of this function (2F51) starts (Yes) or not (No) the first reclosure shot.
Sh2
: Tripping of this function (2F51) starts (Yes) or not (No) the 2
nd
reclosure shot.
Sh3
: Tripping of this function (2F51) starts (Yes) or not (No) the 3
rd
reclosure shot.
Sh4
: Tripping of this function (2F51) starts (Yes) or not (No) the 4
th
reclosure shot.
I>>
: Minimum phase current pick-up level (limited to 40 times In)
tI>>
: Trip time delay
t2xI
: Trip time delay