MC20-CEI
Doc. N°
MO-0431-ING
Microelettrica Scientifica S.p.A. - Copyright 2009
FW 1080.36.03.X
Date 18.11.2011
Rev.
3
Pag. 24
of 35
12. Menu and Variables
12.1 - Misure in Tempo Reale (
Real Time Measurements
)
Scrolling display of the
Real Time Measurements
is the Default operation.
Scrolling can be stopped at any of the measurements and restarted by pressing the Reset button
.
When stopped on one variable,
appears aside the measurement and the different available measurements
can be selected by the
buttons.
Display
Description
I
= 0 – 65535
%In
Largest of the 3 phase-currents (% of rated current)
IA
= 0 – 65535
A
RMS value of Phase A current (Primary Amps)
IB
= 0 – 65535
A
RMS value of Phase B current (Primary Amps)
IC
= 0 – 65535
A
RMS value of Phase C current (Primary Amps)
Io
= 0.0 – 6553.5
A
RMS value of Zero Sequence Current (Primary Amps)
Vo
= 0 – 65535
V
Zero sequence voltage
alfa0
= 0 – 360
°
Displacement angle Io-Vo
12.2 – Misure (
Instantaneous Measurements
)
Real time measurements can be frozen at any moment selecting the menu “Misure (
Instant Measure
) “:
-
“ Real Time Meas “
-
“Misure “
-
“ 1
st
Measurement
other measurements
-
to go back to “Misure“
Display
Description
I
= 0 – 65535
%In
Largest of the 3 phase-currents (% of rated current)
IA
= 0 – 65535
A
RMS value of Phase A current (Primary Amps)
IB
= 0 – 65535
A
RMS value of Phase B current (Primary Amps)
IC
= 0 – 65535
A
RMS value of Phase C current (Primary Amps)
Io
= 0.0 – 6553.5
A
RMS value of Zero Sequence Current (Primary Amps)
Vo
= 0 – 65535
V
Zero sequence voltage
alfa0
= 0 – 360
°
Displacement angle Io-Vo
12.3 – Cont.Int (
Operation Counters
)
The operation of any of the function here below reported, is counted and recorded in the menu “
Counters
“.
-
“Real Time Measurements“
-
“Cont.Int“
-
“1
st
counters”
other counters
-
to go back to “Real Time Measurements “
Display
Description
I>
=
0 – 65535
Operations counters of first overcurrent element
I>>
=
0 – 65535
Operations counters of second overcurrent element
I>>>
=
0 – 65535
Operations counters of third overcurrent element
Io>
=
0 – 65535
Operations counters of first earth fault element
Io>>
=
0 – 65535
Operations counters of second earth fault element
67S1
=
0 – 65535
Operations counters of first directional earth fault element
67S2
=
0 – 65535
Operations counters of second directional earth fault element
I.R.F.
=
0 – 65535
Operations counters of Internal Relay Fault
DispB
=
0 – 65535
Operations counters of Breaker Discrepancy
BF
=
0 – 65535
Operations counters of Breaker Failure
TCS
=
0 – 65535
Operations counters of trip coil supervision element
HR
=
0 – 65535
Operations counters of HW recovery operations