2.2 Installation

Via positioning hole, use two screws to install the temperature

module to temperature housing or rail.

Figure 2.2 Installation

2.3 Wiring

Figure 2.3 Wiring

Fieldbus temperature transmitter power and bus signal share a

pair of cable, and it is called bus cable. It is suggested the user use

Содержание CS-TT106H-V2.0

Страница 1: ...NCS TT106H V2 0 Intelligent HART Temperature Transmitter User Manual...

Страница 2: ...ieldbus com Warning 1 It is forbidden for users to disassemble the temperature module by themselves 2 Please check if the supply voltage of temperature transmitter meets the power supply voltage requi...

Страница 3: ...number one to be approved internationally in China and the Industrial Ethernet Protocol HSE which is number one to be approved in China and the domestic first fieldbus instrument which has a function...

Страница 4: ...of the Automatic engineering a leading product series a huge market network a strict quality management system and an excellent enterprise culture All these further a solid foundation of entrepreneurs...

Страница 5: ...1 DIMENSION 2 2 2 INSTALLATION 3 2 3 WIRING 3 3 HART TEMPERATURE TRANSMIITER CONFIGURATION 5 3 1TOPOLOGY CONNECTION 5 3 2 FUNCTIONAL CONFIGURATION 6 4 MAINTENANCE 18 5 TECHNICAL SPECIFICATION 20 1 1 B...

Страница 6: ...blocks and realizes not only general measurement function but also complicated control strategy NCS TT106H V2 0 uses digital technology so it can connect with many types of thermocouple and thermo res...

Страница 7: ...Temperature Transmitter NCS TT106 Page Email fang siqi microcyber cn http www microcyber fieldbus com 2 2 1 Dimension Figure 2 1 Dimension of Temperature Transmitter Unit mm 2 INSTALLATION...

Страница 8: ...2 2 Installation Via positioning hole use two screws to install the temperature module to temperature housing or rail Figure 2 2 Installation 2 3 Wiring Figure 2 3 Wiring Fieldbus temperature transmi...

Страница 9: ...crocyber fieldbus com 4 fieldbus special cable recommended by IEC61158 2 The signal cable and bus cable cannot share wires or wire slot with other device power wire and they shall be away from device...

Страница 10: ...ded into 4 20mA compatible mode and networking mode 4 20mA compatibility mode as shown in Figure 3 1 TT106 HART HART 2 3 Figure 3 14 20mA compatible mode Features 1 Access to the upper level control s...

Страница 11: ...rts up to 64 device networking in short address format 3 2 Functional configuration The intelligent temperature transmitter supports Microcyber Corporation s HartMPT configuration software HART FCG s...

Страница 12: ...ne device and can also set the fixed current output 5 Variable monitoring It can periodically refresh all dynamic variables of the selected online device and display the trend curve of the current dev...

Страница 13: ...device by pressing the Apply button 1 The selection range of the address is 0 to 63 2 The message can be entered up to 32 characters 3 Description can input up to 16 specified characters 4 The maximum...

Страница 14: ...ce output variables main variable cold junction temperature value current value percentage setting of main variable information damping value unit range upper limit range lower limit calibration of ra...

Страница 15: ...h alarm it can be 21 75mA to 23 00mA The alarm current is set within the range when the alarm type is low alarm the alarm current can be set within the range of 3 50mA to 3 75mA After the information...

Страница 16: ...ormation tab allows you to view the currently configured sensor information upper lower and minimum spans and to configure each sensor type line and other information As shown in Figure 3 5 Figure 3 5...

Страница 17: ...m 3 wire system and 4 wire system only effective for RTD Cold end temperature compensation it can be set to prohibit internal measurement and external measurement When the cold end temperature compens...

Страница 18: ...connected to RTD in 2 wire mode to avoid the error caused by the resistance on the cable the sensor end can be short connected and then the zero calibration button can be executed to eliminate the err...

Страница 19: ...n series in the output circuit of the equipment 2 Set the polling address of the device to be 0 Refer to the basic information configuration If the polling address is 0 you can skip this step 3 Enter...

Страница 20: ...he button alternately displays Enter Fixed Current Mode and Exit Fixed Current Mode to prompt the user to operate HART intelligent transmitter continuously compares main variable value with the upper...

Страница 21: ...is 0 Other polling addresses are in complete digital communication mode which will prompt the error message command execution failure Variable monitoring Through the variable monitoring tab all dynam...

Страница 22: ...Temperature Transmitter NCS TT106 Page Email fang siqi microcyber cn http www microcyber fieldbus com 17 Figure 5 2 Variable monitoring...

Страница 23: ...dule Failure Replace the temperature module with others for testing Reading Error Temperature Module Connection Failure Check sensor short circuit open circuit and earthing Check sensor Noise Disturb...

Страница 24: ...Temperature Transmitter NCS TT106 Page Email fang siqi microcyber cn http www microcyber fieldbus com 19 Check function block parameter configuration...

Страница 25: ...ltage signal Channel Single RTD Wiring 2 wire 3 wire 4 wire Bus Power HART 11 35 VDC Bus Signal HART current mode Electric isolation 1000VAC Working Temperature 40 85 Humidity Range 5 95 RH Start Time...

Страница 26: ...0 500 0 04 0 001 0 4000 0 35 0 015 PT100 200 850 0 15 0 003 PT1000 200 850 0 15 0 005 CU50 50 150 0 15 0 005 CU100 50 150 0 10 0 003 RTD Other Parameter Wiring 2 3 4 Common Mode Rejection 70dB 50Hz an...

Страница 27: ...N 190 1300 0 50 0 015 R 0 1768 0 75 0 023 S 0 1768 0 70 0 023 T 200 400 0 35 0 015 Thermocouple Other Parameter Compensation Accuracy 0 5 Sensor Type B E J N K R S T 100mV 100mV Common Mode Rejection...