To change the 

BATTERY CHARGE

 menu push ENTER, the following will show: 

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
                       
                      

This allows the user to program the charge rate from 0 to 100%. LEVEL 4 is the factory 

default. Level 1 is 0%, Level 2 is 5%, Level 3 is 25%, Level 4 is 50%, Level 5 is 75%, 
Level 6 is 100%. 

 

INVERTER 

CHARGE AMPS 

1Kw12V 

40A 

1Kw24V 

30A 

1Kw36V 

20A 

1Kw48V 

10A 

2Kw12V 

80A 

2Kw24V 

40A 

2Kw36V 

30A 

2Kw48V 

20A 

3Kw24V 

60A 

3Kw36V 

40A 

3Kw48V 

30A 

5Kw24V 

100A 

5Kw36V 

75A 

5Kw48V 

50A 

 
 

Above is the list of charge amps for all of the inverters. 

 
In regards to the battery charge level – The Level selected will allow the battery charge to 
the batteries. 
 
LEVEL 3 – 25% – On a 5Kw48V Inverter will allow a charge of 12.5A to the battery. 
LEVEL 5 – 75% – On a 5Kw48V Inverter will allow a charge of 37.5A to the battery. 
 
 
 

BATTERY 

 

CHARGE                  

LEVEL (X)   

SELECTED 

MICROCARE 

ON 

OFF 

ENTER 

Menu Down 

Menu Up 

OK 

Inverter 

Error

Содержание 12/1000

Страница 1: ...0 1Kw 2Kw 3Kw 5Kw PURE SINE WAVE BI DIRECTIONAL INVERTER MANUAL...

Страница 2: ...1 Contents 1 INTRODUCTION 2 2 SAFETY INSTRUCTION 3 3 SYSTEM DESCRIPTION 6 4 INVERTER OPERATION 8 5 INVERTER PROGRAMMING 13 6 SPECIFICATIONS OF INVERTERS 23...

Страница 3: ...atible with both linear and non linear loads 1 2 3 24 hour operation of the inverter 1 2 4 DC start and automatic self diagnostic function 1 2 5 THD less than 3 1 2 6 Internal high power 3 stage charg...

Страница 4: ...e sure the BATTERY INPUT CIRCUIT BREAKER is OFF 2 2 5 Place cables in such a way that no one can step on or trip over them 2 2 6 Battery cables must be a minimum of 35mm and as short as possible 2 2 7...

Страница 5: ...are inverter is designed primarily for Grid Mains connection to include charging When Mains is connected to the inverter the Neutral connection is Earthed via the Mains If the Inverter is connected as...

Страница 6: ...r this purpose You can now fit an earth leakage after the inverter But if you are going to supply your inverter with AC from the grid then you need to put the inverter before the earth leakage and you...

Страница 7: ...precautionary measures specified below and any other measures necessary when working with batteries Remove wristwatches rings and other metal objects Use only tools with insulated grips and handles 3...

Страница 8: ...ressed with the UP Key to turn on the UPS Push the ENTER button to confirm or store DATA 3 2 5 Push the UP and DOWN keys together to turn off the inverter 3 2 6 Fault LED Red To indicate the INVERTER...

Страница 9: ...INVERTER rating 4 2 Operation Procedure Please follow the instructions below for the UPS operation Push and hold the RED PRECHARGE BUTTON until the Display comes on and shows the following The displa...

Страница 10: ...en changes to While holding in the PRECHARGE BUTTON turn on the MAIN CIRCUIT BREAKER UPS TURNED OFF MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error UPS TURNED OFF CALIBRATING MICROCARE ON O...

Страница 11: ...Down key are pressed simultaneously for 3 seconds the UPS will be turned OFF after two beeps LCD DISPLAY MENU With the inverter in the ON position use the Up Down keys to select menu displays of the L...

Страница 12: ...voltage and amps that the load is drawing from the Inverter This shows the internal temperature of the UPS TEMPERATURE 26 3 deg cel MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error UPS VOLTS...

Страница 13: ...ve a 100 communication level This indicates the serial number of the Inverter SERIAL NUMBER MCxx007 MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error SIGNAL STRENGTH DISPLAY UPS 100 MICROCARE...

Страница 14: ...hing ENTER you can change whether the inverter runs in MANUAL mode AUTO mode or SOLAR mode In the AUTO mode the inverter uses the least amount of battery power when there is no load however AUTO mode...

Страница 15: ...Value setup in the SETUP MENU When the inverter is running in solar control mode and the Charge level is set to LEVEL 1 the inverter will run the load using mains power and the solar regulator will ch...

Страница 16: ...can be changed Push the UP button The menu changes to AC RUN TO menu Allows the user to set the level the mains will charge the battery to before the inverter switches back to battery power AC Run To...

Страница 17: ...y be changed thru 5 LEVELS The factory default level is 2 Level 1 is HIGH and 2 is MEDIUM These are instant trips Levels 3 and 4 are HIGH and MEDIUM but have a 3 retry operation If the inverter trips...

Страница 18: ...display will show EXIT DO NOT SAVE SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error RESTORE FACTORY SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error EXIT AN...

Страница 19: ...will show If no entry is made for 1 minute the display will return to the main menu and the back light will turn off Use the UP button to select BATTERY menu ENTER BATTERY MENU MICROCARE ON OFF ENTER...

Страница 20: ...w12V 80A 2Kw24V 40A 2Kw36V 30A 2Kw48V 20A 3Kw24V 60A 3Kw36V 40A 3Kw48V 30A 5Kw24V 100A 5Kw36V 75A 5Kw48V 50A Above is the list of charge amps for all of the inverters In regards to the battery charge...

Страница 21: ...1 is the lightest load to the generator while LEVEL 6 is the maximum The factory default LEVEL is 1 This only needs to be adjusted if there is a generator connected When a generator is running the gen...

Страница 22: ...t MENU is This allows the user to select the TIME that the BOOST VOLTAGE will be held at before changing to FLOAT By pushing ENTER you can select 1 2 or 3 hours BATTERY BST TIME BST FOR 1 HOUR MICROCA...

Страница 23: ...er is in FLOAT but you require it to go back into BOOST then the next menu will allow this Pushing the ENTER button allows the charge to be changed from AUTO to BOOST or FLOAT Push the UP button This...

Страница 24: ...tage range 3 RMS for entire battery voltage range Frequency 50Hz 50Hz Frequency Regulation 0 1Hz 0 1Hz Power Factor 1 1 Wave Form Pure Sine Wave Pure Sine Wave Efficiency 96 96 Circuit Breaker Circuit...

Страница 25: ...50Hz 50Hz Frequency Regulation 0 1Hz 0 1Hz 0 1Hz 0 1Hz Power Factor 1 1 1 1 Wave Form Pure Sine Wave Pure Sine Wave Pure Sine Wave Pure Sine Wave Efficiency 90 90 90 90 Circuit Breaker Circuit Breake...

Страница 26: ...Vac Amps 22 amps Voltage Regulation 3 RMS for entire battery voltage range Frequency 50Hz Frequency Regulation 0 1Hz Power Factor 1 Wave Form Pure Sine Wave Efficiency 90 Circuit Breaker Overload Pro...

Страница 27: ...Regulation 0 1Hz 0 1Hz 0 1Hz 0 1Hz Power Factor 1 1 1 1 Wave Form Pure Sine Wave Pure Sine Wave Pure Sine Wave Pure Sine Wave Efficiency 96 96 90 90 Load 96 Circuit Breaker Circuit Breaker Circuit Bre...

Страница 28: ...of terminals When considering any electronic breakage except due to lightning reverse polarity over voltage etc the state of the internal control circuitry determines the warranty This warranty will n...

Страница 29: ...d from Microcare and we require the following information 1 Details of the item s you would like to return 2 Our invoice number 3 The reason for the return 4 Microcare must be notified within 7 days o...

Отзывы: