RFT9739 Rack-Mount Transmitter Instruction Manual
Troubleshooting
continued
Table 7-7. Default values after a master reset
Characterization variables
Default
Default
Flow calibration factor
1.00005.13
Mass flow factor
1.0
Density
Volume flow factor
1.0
Density A
0.0000 g/cc
Density factor
1.0
K1 density constant
5000.00
Pressure
Density B
1.0000 g/cc
Pressure polling
No
K2 density constant
50000.00
Field device tag
DP CELL!
Density temperature coefficient
4.44% per 100°C
Pressure input at 4 mA
0.00 psi
FD density constant
0.000
Pressure input at 20 mA
1000.00 psi
Temperature calibration factor
1.00000T0000.0
Pressure correction for flow
0.00% per psi
Pressure correction for density
0.00 g/cc per psi
Flow calibration pressure
0.00 psi
Measurement units
Default
Default
Mass flow unit
g/sec
Temperature unit
°C
Volume flow unit
l/sec
Pressure unit
psi
Density unit
g/cc
Field device variables
Default
Default
Mass flow cutoff
0.00 g/sec
Low slug flow limit
0.0000 g/cc
Volume flow cutoff
0.0000 l/sec
High slug flow limit
5.0000 g/cc
Flow direction
Forward only
Internal damping on density
2.00 sec
Internal damping on flow
0.80 sec
Internal damping on temperature
4.00 sec
Transmitter output variables
Default
Default
Primary mA output variable
Mass flow
Frequency/pulse output variable
Mass flow
Upper range value
160.00 g/sec
Frequency
10000.00 Hz
Lower range value
–160.00 g/sec
Rate
15000.00 g/sec
Added damping
0.00 sec
Maximum pulse width
0.50 sec
Secondary mA output variable
Temperature
Control output
Flow direction
Upper range value
450.00°C
Slug duration
1.00 sec
Lower range value
–240.00°C
Polling address
0
Added damping
0.00 sec
Burst mode
Off
Device information
Default
Default
Transmitter tag name
M
.
RESET
Sensor model
Unknown
Description
CONFIGURE
XMTR
Sensor flow tube material
Unknown
Message
MASTER
RESET
-
ALL
DATA
DESTROYED
Sensor flange type
Unknown
Sensor flow tube liner material
None
Date
01/
JAN
/1995
Communication settings
Default with switch 5* set to STD COMM
Default with switch 5* set to USER DEF
Stop bits and parity
1 stop bit, odd parity
1 stop bit, odd parity
Protocol, physical layer, baud rate
HART Bell 202 on primary mA at 1200 baud,
and Modbus RTU on RS-485 at 9600 baud
HART on RS-485 at 1200 baud
*For information about switches and switch settings, see Section 2.3, page 5.
Содержание Fisher Rosemount RFT9739
Страница 1: ...Model RFT9739 Rack Mount Transmitter Instruction Manual Version 3 Transmitters February 2000 ...
Страница 2: ......
Страница 4: ......
Страница 20: ...10 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 26: ...16 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 92: ...82 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 100: ...90 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 110: ...100 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 112: ...102 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 120: ...110 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 122: ...112 RFT9739 Rack Mount Transmitter Instruction Manual ...
Страница 129: ......