Page 32
Mounting and Installation
scanCONTROL 25xx
5.3
Installation Instructions
- Only use shielded cables from the accessories for all connection cables, see Chap.
.
- Connect the cable shields to the potential equalization on the evaluation unit (switch cabinet, PC housing,
connector housing) and avoid ground loops.
- Lay all connection cables in accordance with the generally applicable measuring technology regulations,
i.e. for example not directly next to pulse-carrying lines, preferably in a separate cable duct.
- The minimum bending radii of the recommended cables for flexible laying must not be less 80 mm.
- MICRO-EPSILON recommends the use of the optionally available power supply PS2020, Din rail mounting,
input 230 VAC, output 24 VDC/2.5 A.
5.4
Getting Ready for Operation, Commissioning
Mount the sensor according to the installation instructions, see Chap.
Connect the sensor to the Ethernet cable.
Connect the sensor to downstream display or monitoring units and to the power supply.
Switch on the power supply.
The sensor must only
be connected to the
peripheral equipment
when disconnected
from the power supply.