6.3.26
Analog Math Function (AMF)
Analog outputs of the IF1032 can be reckoned up here and the result is output via channel 4. Units of the
inputs are not considered.
Command
$AMF<Offset>,<Factor1>,<Factor2>,<Factor3><CRLF>
Response
$AMF<Offset>,<Factor1>,<Factor2>,<Factor3>OK<CRLF>
Parameter
Offset, Factor 1, Factor 2, Factor 3 = float, with this factor the respective ana-
log output is multiplied
Example
$AMF100,1.25,-2,0<CR> (sets a math function with offset 100, analog chan-
nel 1 is multiplied with factor 1.25, analog channel with -2 and the total is
output
Request
$AMF?<CR>
Delete math
function
$AMF0<CR><
6.3.27
Default Messages
- Unknown command: (ECHO) + $UNKNOWN COMMAND<CRLF>
- Wrong parameter after command: (ECHO) + $WRONG PARAMETER<CRLF>
- Timeout (approximately 10 s after last input) (ECHO) + $TIMEOUT<CRLF>