Page 23
Installation and Commissioning Instructions
thicknessCONTROL MTS 8202.LLT / 4350127.256
emergency Stopp
contact : 2
4
PE
5
Connect Analog signal to +ET1-17A1:
Signal
+ET1-17A1
contact
Cable
From ATI
Analog signal
-10V…10V
O1
GND
GND
Shield
Shielding rail cabinet
Connect Ethernet IP to +ET1-9X7
Connect remote support (VPN) to +ET1-9X8
Connect LLT 1 Signal cable -9W4 to +ET1-9X1 and to +CFR-9X2
Connect LLT 2 Signal cable -9W8 to +ET1-9X4 and to +CFR-9X5
Connect 24V/Dig I/O C-frame cable -21W1 to +ET1-21X1 and to +CFR-21X2
Connect motorcable -17W1 to +ET1-17A2 and to +CFR-17M1
Connect 24V/Dig I/O pneumatic unit cable -13W1 to +ET1-13X1
Connect the grounding terminal of the measuring system to the potential equaliza-
tion of the electrical installation using a potential equalization conductor of at least 10
mm².
4.6
Pneumatic Supply
Connect the compressed air supply
Characteristics:
Compressed air:
Nominal pressure max. 6 bar ±5 %, dry
and oil-free
Max. air consumption:
30 l/min
Standard:
DIN ISO 8573-1:2010 [1:4:2]
Содержание 4350127.256
Страница 1: ...thicknessCONTROL MTS 8202 LLT C frame Non contact thickness measurement Operating Instructions...
Страница 10: ...Page 10 Overview Technical Data Safety Instructions thicknessCONTROL MTS 8202 LLT 4350127 256...
Страница 26: ...Page 26 Installation and Commissioning Instructions thicknessCONTROL MTS 8202 LLT 4350127 256...
Страница 56: ...Page 56 Declaration of Incorporation thicknessCONTROL MTS 8202 LLT 4350127 256...
Страница 78: ...Operating Instructions scanCONTROL 29xx...
Страница 82: ...scanCONTROL 29xx Appendix A 1 Accessories 62 A 1 1 Recommended Accessories 62 A 1 2 Optional Accessories 63...
Страница 83: ......
Страница 119: ...Page 42 Operation of the Sensor with a PC scanCONTROL 29xx Fig 23 Predefined measuring fields...