WBV417U01 AC Voltage Transducer 

RMS

 

Safety claim 

The  information  in  the  safety  claim  of  the  equipment  documentation  is  intended  to  ensure  that 
equipment is properly installed in order to maintain it in a condition. 
It is assumed that everyone who would be associated with the equipment should be familiar with 
the contents of that safety section, or this safety guide. 
When electrical equipment is in operation, dangerous voltages will be present in certain parts of 
the  equipment  (e.g.  the  input  terminal).  Failure  to  obverse  warning  notices,  incorrect  use,  or 
improper  use  may  endanger  personnel  and  equipment  and  course  personal  injury  or  physical 
damage. 
Before working in the terminal strip area, the equipment must be isolated. 
Proper and safe operation of the equipment depends on appropriate shipping and handling, proper 
storage, installation and commissioning, and on careful operation, maintenance and servicing. 
The operating manual for the equipment gives instructions for its installation, commissioning, and 
operation.  However,  the  manual  cannot  cover  all  conceivable  circumstances  or  include  detailed 
information  on  all  topics.  In  the  event  of  questions  or  specific  problem,  do  not  take  any  action 
without  proper  authorization.  Contact  the  appropriate  WB  technical  sales  office  and  request  the 
necessary information.   
 

Standard application 

1. Accuracy 

    Accurate degree is conformed to IEC688:1992 

2. Safety 

  2.1 Overload capability 
        Overload capability is conformed to IEC688:1992 
  2.2 Isolation voltage 
        Can be endured testing voltage is conformed to Q/72085584-0.1-2004 
  2.3 Insulation impedance 
        The  insulation  impedance  is  no  less  than  20M  Ohm,  is  conformed  to 

Q/72085584-0.1-2004     

3. Electromagnetic Capability   
     

  3.1 Electromagnetic field immunity test according to IEC 61000-4-3:1995 

3.2 Power frequency magnetic field immunity test according to IEC 61000-4-8:1993     
 

Product Description and Application   

WBV417U01 converts AC input voltage into a load independent output signal DC 4-20mA. It has 
adopted  electromagnetic  isolation  principle  and  RSM  measurement  method  for  real  time 
measurement of AC voltage (in any wave form) from electric net or electric circuit. 

 

Содержание WBV417U01

Страница 1: ...ducer RMS www mywbdz com alex827 qq com Technical Service 86 816 2778271 Quality Complain 86 816 2278273 Fax Line 86 816 2281934 ISO9001 ISO14000 ISO18000 Certified Quality Warranty Any quality problem found in WB series products we offer Three years free charge of repair the products and six months guaranteed free charge of change and return the products ...

Страница 2: ...maintenance and servicing The operating manual for the equipment gives instructions for its installation commissioning and operation However the manual cannot cover all conceivable circumstances or include detailed information on all topics In the event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request...

Страница 3: ...Fax 86 016 2281934 www mywbdz com alex827 qq com 3 3 The product has certain advantages of total galvanic isolation between input output high accuracy low drifting by temperature and wide temperature bearable range etc Function realization schematic drawing Product Dimensional Drawing unit mm In 3 1 12 11 Out 10 11 E G _ _ ...

Страница 4: ...ent Ux 10V Ri Ux 1kΩ V Measurement Ux 10V Ri Ux 10kΩ V 7 Linear Range 0 120 of nominal input 8 Responding Time 300mS 9 Over Load Capacity 2 times of nominal input continuous 10 Maximum Load 6V 11 static current 25mA 12 Auxiliary Power 24V dc 13 Isolation Voltage 2500Vdc for 1 minute 14 Output Ripple 40mV root mean square value output load is 250Ohm 15 Drifting by Temperature 5 10 3 16 Ambient Temp...

Страница 5: ...ately But for further precise signal sampling user needs to warm up the product for 3 minutes before use a The auxiliary power requires isolation voltage 2000VAC DC current output ripple 10mV and multiple converters can share with one set auxiliary power together b Output signal Iz is designed to follow the impedance load value of 250Ω When Resistance R1 is less than 100Ω the user must add output ...

Страница 6: ...and polarity other wise will damage the product 2 Pay attention to the wire connection wrong terminal connection will cause malfunction of the product and even damage the product 3 Don t dismantle the product and carry with care to avoiding bump and fall of the product 4 If the product has been using under the environment with strong magnetic field interference please pay attention to the shield o...

Страница 7: ...year warranty of free charge of repairing the product and any purchase made in six months Weibo will provide free charge of change and return the product if damage and problem caused by product quality Note Transportation fee of repaired and returned product will be borne by Buyer Product Input Output characteristic curve Input 0 100 4mA 20mA Input Output characteristic curve 20 23 2 120 Output mA...