WBV412M05 AC Voltage Sensor 

Safety claim 

The  information  in  the  safety  claim  of  the  equipment  documentation  is 
intended  to  ensure  that  equipment  is  properly  installed  in  order  to 
maintain it in a condition. 
It  is  assumed  that  everyone  who  will  be  associated  with  the  equipment 
will  be  familiar  with  the  contents  of  that  safety  section,  or  this  safety 
guide. 
When  electrical  equipment  is  in  operation,  dangerous  voltages  will  be 
present in certain parts of the equipment (e.g. the input terminal). Failure 
to obverse warning notices, incorrect use, or improper use may endanger 
personnel and equipment and course personal injury or physical damage. 
Before working in the terminal strip area, the equipment must be isolated. 
Proper  and  safe  operation  of  the  equipment  depends  on  appropriate 
shipping  and  handling,  proper  storage,  installation  and  commissioning, 
and on careful operation, maintenance and servicing. 
The  operating  manual  for  the  equipment  gives  instructions  for  its 
installation, commissioning, and operation. However, the manual cannot 
cover all conceivable circumstances or include detailed information on all 
topics.  In  the  event  of  questions  or  specific  problem,  do  not  take  any 
action  without  proper  authorization.  Contact  the  appropriate  WB 
technical or sales office and request the necessary information.   

 
Standard application 

1. Accuracy 

    Accurate degree is conformed to IEC688:1992 

2. Safety 

2.1 Overload capability 
      Overload capability is conformed to IEC688:1992 
2.2 Isolation voltage 

Can be endured testing voltage is conformed to 
Q/72085584-0.1-2004 

2.3 Insulation impedance 

The insulation impedance is no less than 20M Ohm, is conformed to 

Содержание WBV412M05

Страница 1: ...upplying WB Series Electric Isolated Sensor and Digital Electrical Sensor since 1989 USER MANUAL WBV412M05 AC voltage sensor www wbsensor com wbwm wbdz cn Tel 86 0816 2971265 Fax 86 0816 2281934 ISO9001 ISO14000 ISO18000 Certified ...

Страница 2: ...amage Before working in the terminal strip area the equipment must be isolated Proper and safe operation of the equipment depends on appropriate shipping and handling proper storage installation and commissioning and on careful operation maintenance and servicing The operating manual for the equipment gives instructions for its installation commissioning and operation However the manual cannot cov...

Страница 3: ... uses a special isolation module to measure the AC voltage in the grid and circuit in real time and convert it into DC voltage Uz output It has advantages of high precision high isolation low power consumption low drift wide temperature range and anti interference strong ability wide working power range and so on This product adopts card mounted structure terminal wiring easy installation three is...

Страница 4: ...Over Load Capacity 2 times of nominal input continuous 8 Maximum Load output current 5mA 9 Auxiliary Power 9V 36V DC 10 Isolation Voltage Input Output 2500Vdc for 1 min Input power supply 2500Vdc for 1 min Output power supply 2500Vdc for 1min 11 Output Ripple 10mv 12 Drifting by Temperature 150 10 6 13 Ambient Temperature 25 70 14 Mounting DIN Rail 35mm Mount The undefined terminals in the diagram...

Страница 5: ...criterion A Instruction of Installation and Use 1 The product has adopted structure compliance with EN50022 suitable for DIN rail mounting NS35 7 5 NS35 15 Installation steps are as following please reference to dimensional drawing Step 1 Immobilize one side of product s mounting trough to the DIN mounting rail Step 2 Pull out the spring clasp Step 3 Place whole mounting trough to the DIN mounting...

Страница 6: ... the sensor for 3 minutes 4 using output monitoring meter V1 to measuring the output of signal power source instrument set a any input value which is within the measuring range of the sensor Vr for e g if input value is 100V the output is 0 5V the expected output value Vz should be calculated as Vz 5V 0V Vr 100V 5 using output monitoring meter V2 to measuring the output voltage V0 of the sensor th...

Страница 7: ...iding bump and fall of the product 4 If the product has been using under the environment with strong magnetic field interference please pay attention to the shield of input wire and the output signal wire should be as short as possible For product intensive installation the space between each product should not be smaller than 10mm 5 Only use identified terminals 6 There is no lightning strike pre...

Отзывы: