background image

 

2

WBV334U01 DC Voltage Transducer 

Safety claim 

The information in the safety claim of the equipment documentation is intended to ensure that 
equipment is properly installed in order to maintain it in a condition. 
It is assumed that everyone who would be associated with the equipment should be familiar with 
the contents of that safety section, or this safety guide. 
When electrical equipment is in operation, dangerous voltages will be present in certain parts of 
the equipment (e.g. the input terminal). Failure to obverse warning notices, incorrect use, or 
improper use may endanger personnel and equipment and course personal injury or physical 
damage. 
Before working in the terminal strip area, the equipment must be isolated. 
Proper and safe operation of the equipment depends on appropriate shipping and handling, proper 
storage, installation and commissioning, and on careful operation, maintenance and servicing. 
The operating manual for the equipment gives instructions for its installation, commissioning, and 
operation. However, the manual cannot cover all conceivable circumstances or include detailed 
information on all topics. In the event of questions or specific problem, do not take any action 
without proper authorization. Contact the appropriate WB technical sales office and request the 
necessary information.   
 

Standard application 

1. Accuracy 

    Accurate degree is conformed to IEC688:1992 

2. Safety 

  2.1 Overload capability 
        Overload capability is conformed to IEC688:1992 
 2.2 Isolation voltage 
        Can be endured testing voltage is conformed to Q/72085584-0.1-2004 
  2.3 Insulation impedance 
    The insulation impedance is no less than 20M Ohm, is conformed to 

Q/72085584-0.1-2004   

3. Electromagnetic Capability   

 

 

 

 

 

3.1 RF-Electromagnetic field immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001 

3.2 Power frequency magnetic field immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001  

3.3 Electrostatic discharge immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001 

3.4 Surge immunity test according to EN61000-6-2:2005, EN61000-6-4:2001 
3.5 Electrical fast transient/burst immunity test according to EN61000-6-2:2005, 

EN61000-6-4:2001 

3.6 Conducted disturbance voltage according to EN61000-6-2:2005, EN61000-6-4:2001 

Mianyang Weibo Electronic Co.,Ltd 

No.7 Road 2 of Xianren Road Youxian District Mianyang City P.R. China     

Tel: 86-816-2971265 Fax: 86-816-2281934 

www.wb-my.com

2

     

[email protected]

 

 

Содержание WBV334U01

Страница 1: ...nsducer www wb my com wblch wbdz cn Technical Service 86 816 2278271 Quality Complain 86 816 2278273 Fax Line 86 816 2281934 ISO9001 ISO14000 GB T2800 CE Certified Quality Warranty Any quality problem found in WB series products we offer Three years free charge of repair the products and six months guaranteed free charge of change and return the products ...

Страница 2: ...d information on all topics In the event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request the necessary information Standard application 1 Accuracy Accurate degree is conformed to IEC688 1992 2 Safety 2 1 Overload capability Overload capability is conformed to IEC688 1992 2 2 Isolation voltage Can be ...

Страница 3: ...ulation demodulation isolation principle and average measurement method for real time measurement of DC voltage sine wave form from electric net or electric circuit The product has certain advantages of total galvanic isolation between input output high accuracy low drifting by temperature and wide temperature bearable range etc Function realization schematic drawing In 3 1 12 11 Out 10 11 E G _ _...

Страница 4: ... 5 Linear Range 0 120 of nominal input 6 Responding Time 350ms 7 Over Load Capacity 2 times of nominal input continuous 8 Maximum Load 6V 9 Auxiliary Power 24V 10 Current consumption for static status 17mA 11 Isolation Voltage 2500Vdc for 1 minute 12 Output Ripple 10mV root mean square value output load is 250Ohm 13 Drifting by Temperature 0 50 2 5 10 4 25 0 50 70 3 5 10 4 14 Ambient Temperature c...

Страница 5: ...10mV and multiple converters can share with one set auxiliary power together b When measuring dc voltage exceeds 1000volts the circuit needs adding a resistor to divide the input dc voltage The resistor is provided by Weibo Electronic and only for each type of transducers special use only 3 Transducer VX 4 Resistor C When measuring DC voltage less than 600V uses terminals 3 and 1 for connection wh...

Страница 6: ...fied Caution 1 Pay attention to the auxiliary power information especially the auxiliary power grade and polarity other wise will damage the product 2 Pay attention to the wire connection wrong terminal connection will cause malfunction of the product and even damage the product 3 Don t dismantle the product and carry with care to avoiding bump and fall of the product 4 If the product has been usi...

Страница 7: ...new and shall comply in all respects with the Technical Specification confirmed with Buyer b Warranty Period Three year warranty of free charge of repairing the product and any purchase made in six months Weibo will provide free charge of change and return the product if damage and problem caused by product quality Note Transportation fee of repaired and returned product will be borne by Buyer Pro...

Отзывы: