background image

8

Caution:

Inadequate  water  flow  to  heat  exchanger  due  to

improper pipes, valves or pump is dangerous to heat pump

and  constitutes  abuse  that  will  void  the  warranty  of  the

compressor and/or heat exchanger.
An in-line water screen strainer is always recommended but

it  is  imperative  where  poor  water  quality  may  exist.  Ball

valves  with  hose connections  are  recommended  for  back-

flushing and chemical cleaning of the evaporator condenser.

Condensate Piping

A drain trap must be connected to the drain pan at the unit.

A  condensate  connection  is  provided  on  each  side  of  the

unit.  Condensate  piping should  be  installed  according  to

local codes. The line should be one size larger than pipe size

as the drain nipple and should pitch downward toward the

building drain.

Do not over tighten the connect-

ions.  The  connection  to  the  unit

needs to be hand tightened.

Connect drain line to the unit with a “P” trap to avoid pull-

ing  air  from  outside  the  unit  back  through  the  drain  line.

The line should be insulated where the ambient conditions

may  cause  a  condensation  on  the  surface  of  the  pipe.  An

additional  drain  pan  may  be  installed  under  the  unit,  and

should include a separate drain line for overflow from the

primary drain. An air break should be used with long runs of

condensate lines.
Drain  pans  in  any  air  conditioning  equipment,  even  when

they  have  a built-in  slope  to  the  drain,  will  have  moisture

present  and  will  require  periodic  cleaning  to  prevent  any

build-up of algae or bacteria. Cleaning of the drain pans will

also  prevent  any  possible  plugging  of  the  drain  lines,  and

overflow of the pan itself. Some means to clean out the “P”

trap  should  be  provided.  Only  qualified  personnel  should

clean drain pans, drain lines or the insides of equipment.

Electrical

WARNING!

All electrical works need to  be performed by a licensed

electrician and according to all applicable codes.

Check the unit data plate to make sure it matches with the

power  supply.  Proper  fuses  or  HACR  circuit  breakers

should  be  installed.  See  unit’s  nameplate  for  minimum

amps  and  maximum  fuse/breaker.  Connect  power  to  the

unit  according to  the  wiring  diagram  provided  with  the

unit.

Use  ONLY  copper  wires  for

power lines.

The  power  and  control  wiring  may  be  brought  into  unit

through the holes provided  on the unit’s cabinet. Protect

the branch circuit in accordance with code requirements.
HPXVS control  wires  should not run with any other wires

inside same conduit.
The units must be electrically grounded in accordance with

all applicable codes.
Power can be applied to the unit after the control wiring is

connected, and start-up checks are complete.

Wall Thermostat / Handset

The low voltage wall thermostat / wired handset should be

located in the air conditioned space on an inside wall 4.5 to

5.5 feet above the floor where it will not be subjected to

drafts, sun exposure or heat from electrical fixtures or app-

liances. Control wire size must be large enough to prevent

excess voltage drop that may cause improper operation of

the equipment. Follow the manufacturer’s instructions en-

closed with thermostat for general installation procedure.
A

Miami  Heat  Pump’s

HPXVS  model  is  furnished  with  its

own  Wall  Handset.  For  this  unit  four  (4)  telephone  wires

are  sufficient  in  size  but  in  case  of  a  unit  replacement

installer may use existing  wires. For a HPXVS unit, please

refer to the handset manual (control spec. for HPXVS unit)

supplied with the unit.

Filters

Slide correct filter in with arrow pointing towards the blo-

wer in the direction of airflow. Make sure filter(s) cover the

entire coil(s).

Содержание HPX Series

Страница 1: ...words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert reader that personal injury and or equipment damage may result if installation and or service are not handled properly Rev 022014003 MIAMI HEAT PUMP ...

Страница 2: ... and Installation Clearance Mounting and Suspension Duct Work Sealing Supplementary Cooling Heating Water Line Piping Condensate Piping Electrical Wall Thermostat Handset Filters 4 Completion General Check out Start up Commissioning 5 Operation and Maintenance General Maintenance and Schedule Filters Blower Assembly Indoor Coil s Water Heat Exchanger Service 6 Troubleshooting ...

Страница 3: ...coil expansion valve reversing valve centrifugal blower high efficiency motor a control panel with all necessary protection devices and safety circuit Units are designed to operate with an entering water temp erature between 50 0 F and 100 0 F suitable for a cooling tower boiler application but an extended range is available down to 25 0 F for Geo Thermo applications for a Geo Thermo application s...

Страница 4: ...nce can cause property damage personal injury or loss life A qualified installer or service agency must perform installation and service RISK OF ELECTRICAL SHOCK Unit may have multiple power supplies Turn the electrical power of the unit OFF and disconnect switch es before attempting to perform any service or maintenance RISK OF INJURY FROM HOT PARTS Discon nect all power close all isolation valve...

Страница 5: ... file a freight claim and to schedule an inspection 5 After losses have been acknowledged by the freight carrier call the factory for a repair or replacement part quote at 866 407 8535 6 With permission of freight carrier order parts and or make repairs 7 If repairs must be made to damaged goods certain equipment alteration repair and manipulation of equipment without the manufacturer s consent ma...

Страница 6: ...t is constructed of sturdy materials it is advised to avoid impacts and handling methods that may damage internal apparatus and struc ture or the exterior surfaces of the unit Take care not to apply destructive force to coils coil and drain stub outs or other parts protruding beyond the extents of the unit casing Always handle the unit by its exterior casing and never by any of the protruding part...

Страница 7: ...he unit is installed in an unconditioned area Supplementary Cooling Heating When heat is called for unit shall switch to mechanical heating Should the unit have hot water or steam capabilities it shall be activated according to controls Unit with Hot Water Coil Water supply lines must be insulated properly fastened drained and supported according to the local code require ments Unit with Steam Coi...

Страница 8: ...nel should clean drain pans drain lines or the insides of equipment Electrical WARNING All electrical works need to be performed by a licensed electrician and according to all applicable codes Check the unit data plate to make sure it matches with the power supply Proper fuses or HACR circuit breakers should be installed See unit s nameplate for minimum amps and maximum fuse breaker Connect power ...

Страница 9: ... a free spinning blower wheel and wheel fitting access pan els Air handlers should not be operated without proper ductwork and access panels installed except as required during start up and air balancing 1 Check all electrical connections to be sure they are tight 2 Open all access panels and remove all shipping screws or restraints 3 Clean out any debris that may have been left 4 Check belt align...

Страница 10: ...ualified personnel should not attempt to adjust air circulation as all system has unique operating characteristics Professional air balance specialists should be employed to establish actual operating conditions and to configure the air delivery sys tem for optimal performance Water Balancing When unit is one of many at the same water system a specialist with a complete working knowledge of water ...

Страница 11: ... wheels are necessary to reduce electrical use maintain capacity and reduce stress on the unit The blower wheel and blower section need to be ins pected periodically and cleaned of dust or debris To ins pect and clean the blower set thermostat to OFF position turn the electrical power to the unit to OFF position at the disconnect switch Clean the assembly check for looseness check screws for tight...

Страница 12: ...m refrigerant evacuate and recharge with factory recommended charge High Pressure Check defective or improperly calibrated high pressure switch Unit OFF on low pressure switch Suction Pressure too Low In COOLING mode lack of or inadequate air flow Entering air temperature too cold Blower inoperative clogged filter or restriction in ductwork In HEATING mode lack of or inadequate water flow Entering...

Отзывы: