Inspect  coils,  clean  if  dirty  or  obstructed  in  any

way.

In  case  of  excessive  noise  or  unusual  operation

check for reason and act accordingly.

Quarterly:

Check cooling coil drain pan and accessible conden-

sate pipes and “P” trap to assure proper drainage.

Clean if necessary.

Check  operation  of heating  and  cooling  section  if

seasonal.

Check the inlet and outlet air temperatures. Deter-

mine cause for abnormal changes and act accord-

ingly.

Check  water  pressure  drop  to  determine  water

flow, in case flow rate is out of range adjust water

flow with unit’s valves.

Annually:

Inspect and clean unit interior as necessary at the

beginning of cooling season mode.

Clean the drain line, “P” trap, and condensate pan.

Clean evaporator coil.

Clean the water to refrigerant heat exchanger.

Check  refrigerant  pressures  and  temperatures

every spring and correct unusual operation accord-

ingly.

Filters

When  the  heat  pump  circulates  and  filter  the  air  in  your

house, dust and dirt particles build up on the filter. Exces-

sive accumulation can block the airflow, forcing the unit to

work harder to maintain desired temperatures, thus costing

more.  Check  filter  at  least  once  a  month  and  change  as

needed with the same size filter. Filters on HPX heat pump

units  are  easy  to  change  as  they  slide  out  of  side  of  unit

easily.  Replace  old  filters  with  the  size  indicated  on  each

filter or as shown in the specific unit data. Be sure arrows

on filter frames point toward the unit.

Blower Assembly

HPX  water  source  heat  pumps  use  forward  curved  blower

wheels  that  are  non-overloading,  very efficient  and  very

easy  clean.  Clean  blower  wheels  are  necessary  to  reduce

electrical  use,  maintain  capacity  and  reduce  stress  on  the

unit. The blower wheel and blower section need to be ins-

pected  periodically,  and  cleaned  of  dust  or  debris. To  ins-

pect and clean the blower, set thermostat to “OFF” position’

turn the electrical power to the unit to “OFF” position at the

disconnect switch. Clean the assembly, check for looseness,

check  screws  for  tightness,  rotate  blower  wheel  while

listening close for noise or roughness.

Indoor Coils

Coils should be inspected and cleaned annually to ensure

there  is  no  obstruction  to  airflow.  Dirty  evaporator  coils

will eventually freeze up, and often result in time consum-

ing and expensive service call. Clean filters will help to pre-

vent  dirt  from  accumulating  on  the  evaporator;  however

the  evaporator  should  be  cleaned  annually  with  a  soft

bristled  brush  and  steam  or  a  non-corrosive  coil  cleaning

solution.  Move  the  brush  in  the  fin  direction.  Make  sure

coil fins are not flattened.

Water Heat Exchanger

The  efficiency  of  the  unit  is  dependent  on  the  water  to

refrigerant  heat  exchanger’s  performance.  Therefore,  a

clean heat exchanger and a correct flow rate are impera-

tive  for  minimizing  the  cost  of  operation.  In  severe  cases

dirty heat exchanger or flow rate out of range may cause

the unit to malfunction. Heat exchanger can be cleaned by

back  flushing  with  or  without  the  appropriate  chemical

available  at  a  refrigeration  supply  shop.  To  obtain  the

correct flow rate adjust the water line valves.

NOTE

It  is  important  to  keep  filters,

water heat exchanger, coil and

blower(s) clean.

Service

Before calling, the model and serial number of the unit will

need to be at hand for the warranty service department to

help  answer  questions  regarding  the  unit.

Miami  Heat

Pump’s

Phone:

866-407-8535

Fax:

866-406-6603

Содержание HPX Series

Страница 1: ...words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert reader that personal injury and or equipment damage may result if installation and or service are not handled properly Rev 022014003 MIAMI HEAT PUMP ...

Страница 2: ... and Installation Clearance Mounting and Suspension Duct Work Sealing Supplementary Cooling Heating Water Line Piping Condensate Piping Electrical Wall Thermostat Handset Filters 4 Completion General Check out Start up Commissioning 5 Operation and Maintenance General Maintenance and Schedule Filters Blower Assembly Indoor Coil s Water Heat Exchanger Service 6 Troubleshooting ...

Страница 3: ...coil expansion valve reversing valve centrifugal blower high efficiency motor a control panel with all necessary protection devices and safety circuit Units are designed to operate with an entering water temp erature between 50 0 F and 100 0 F suitable for a cooling tower boiler application but an extended range is available down to 25 0 F for Geo Thermo applications for a Geo Thermo application s...

Страница 4: ...nce can cause property damage personal injury or loss life A qualified installer or service agency must perform installation and service RISK OF ELECTRICAL SHOCK Unit may have multiple power supplies Turn the electrical power of the unit OFF and disconnect switch es before attempting to perform any service or maintenance RISK OF INJURY FROM HOT PARTS Discon nect all power close all isolation valve...

Страница 5: ... file a freight claim and to schedule an inspection 5 After losses have been acknowledged by the freight carrier call the factory for a repair or replacement part quote at 866 407 8535 6 With permission of freight carrier order parts and or make repairs 7 If repairs must be made to damaged goods certain equipment alteration repair and manipulation of equipment without the manufacturer s consent ma...

Страница 6: ...t is constructed of sturdy materials it is advised to avoid impacts and handling methods that may damage internal apparatus and struc ture or the exterior surfaces of the unit Take care not to apply destructive force to coils coil and drain stub outs or other parts protruding beyond the extents of the unit casing Always handle the unit by its exterior casing and never by any of the protruding part...

Страница 7: ...he unit is installed in an unconditioned area Supplementary Cooling Heating When heat is called for unit shall switch to mechanical heating Should the unit have hot water or steam capabilities it shall be activated according to controls Unit with Hot Water Coil Water supply lines must be insulated properly fastened drained and supported according to the local code require ments Unit with Steam Coi...

Страница 8: ...nel should clean drain pans drain lines or the insides of equipment Electrical WARNING All electrical works need to be performed by a licensed electrician and according to all applicable codes Check the unit data plate to make sure it matches with the power supply Proper fuses or HACR circuit breakers should be installed See unit s nameplate for minimum amps and maximum fuse breaker Connect power ...

Страница 9: ... a free spinning blower wheel and wheel fitting access pan els Air handlers should not be operated without proper ductwork and access panels installed except as required during start up and air balancing 1 Check all electrical connections to be sure they are tight 2 Open all access panels and remove all shipping screws or restraints 3 Clean out any debris that may have been left 4 Check belt align...

Страница 10: ...ualified personnel should not attempt to adjust air circulation as all system has unique operating characteristics Professional air balance specialists should be employed to establish actual operating conditions and to configure the air delivery sys tem for optimal performance Water Balancing When unit is one of many at the same water system a specialist with a complete working knowledge of water ...

Страница 11: ... wheels are necessary to reduce electrical use maintain capacity and reduce stress on the unit The blower wheel and blower section need to be ins pected periodically and cleaned of dust or debris To ins pect and clean the blower set thermostat to OFF position turn the electrical power to the unit to OFF position at the disconnect switch Clean the assembly check for looseness check screws for tight...

Страница 12: ...m refrigerant evacuate and recharge with factory recommended charge High Pressure Check defective or improperly calibrated high pressure switch Unit OFF on low pressure switch Suction Pressure too Low In COOLING mode lack of or inadequate air flow Entering air temperature too cold Blower inoperative clogged filter or restriction in ductwork In HEATING mode lack of or inadequate water flow Entering...

Отзывы: