MHSC MPL11 Скачать руководство пользователя страница 18

18

MPL11 Woodburning Fireplace

87D0173

outside combustion air recommendations

  (continued)

1. Extremely long runs and numerous turns in the duct leading from the fireplace to the combustion air 

assembly should be avoided.  These conditions will increase the resistance to the free flow of air 
through the duct.  Refer to 

Figures 3 and 25

 for methods of installing the outside air for combustion 

assemblies.

2. The combustion air assembly should be located at an exterior location, which is not likely to be ac-

cidentally blocked in any manner.  The assembly should be located above the snow line to prevent 
blockage by snow accumulation.

3. The combustion air inlet assembly should never be mounted in a garage or storage area where com-

bustible fumes such as gasoline might be drawn into the fireplace.

4. Combustion air can be drawn from the crawl space under a house when an adequate supply of air 

is provided by open ventilation.

5. Do not take combustion air from attic space or garage space.

Model ak-4 combustion air assembly

1.  Remove the cover plate from the 4-inch outlet opening location on the left outside of the fireplace.  

DO NOT remove the cover if the outside air will not be connected.

2.  Place the insulation ring between the AK-4 starting collar and fireplace wall and place the starting 

collar (4 inch) into the hole on the left side of the fireplace.  Fasten it in place with the four sheet 
metal screws provided.

3.  Cut  a  6-inch  diameter  opening  for  model AK-4  in  the 

outside  wall  covering  where  the  outside  vent  is  to  be 
located.

4.  Select and cut a piece of duct sufficient length to attach 

to  the  fireplace  and  protrude  at  least  three  inches  be-
yond the face of the wall to which the AK-4 inlet air vent 
will be attached. The duct may be cut with a standard 
pocket knife (use FP-4 U duct for maximum efficiency 
and safety). Do not use a combustible duct. Always use 
UL Listed Class 0 or 1 duct material.

5.  If the duct is the insulated type, push the insulation back 

from one end of the duct approximately two inches.

6.  Slip the exposed end of the duct over the starting collar 

on the fireplace.

7.  Using the sheet metal screws pro-

vided,  secure  the  duct  end  to  the 
collar attached to the fireplace.

8.  Nail  or  screw  the  combustion  air 

assembly  to  the  surface  of  the 
wall.

Note:

  If the wall covering is brick or 

stone,  use  appropriate  masonry  fas-
teners. Mount the combustion air as-
sembly with “TOP’” upward to prevent 
cold air from entering through the wall. 
If it is necessary to splice the duct, a 
model  403-duct  connector  should  be 
used to splice duct sections.

outSide coMbuStioN air

FP1900
OA start collar 
8/08

Insulation Ring

Insert Shortest Side of the 
Tube through the Fireplace 
Outer Wrap to Properly 
Seal Against Firebox Wall 
and Gasket

Longer Length of the 
Tube to Outside

Figure 21

FP1900

FP1901
secure outside duct
8/08

Fireplace Outer Wrap

AK4 Combustion Air 
Kit (Shortest Toward 
Firebox)

AK4 Mounting 
Plate

Firebox Insulation 
Seal

FP1901

Figure 22

Содержание MPL11

Страница 1: ...result To reduce the risk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact local building officials about r...

Страница 2: ...d be aware however that failure to install operate and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths injuries and...

Страница 3: ...eas Intended Product Usage The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with zero clearance to combustible building materials at the side and top sp...

Страница 4: ...located inside the fireplace The counterweighted damper is operated by simply pushing up to open or pulling down to close the damper When the fireplace is not in use the damper should be closed to pr...

Страница 5: ...3 mm 3056M 768 mm 3756M 946 mm 42 1067 mm 45 6M 1162 mm 36 914 mm 38 965 mm 23 584 mm 1 2 13 mm 14 6 378 mm 856O 216 mm 12 305 mm 24 610 mm 22 6M 578 mm 9 229 mm 12 305 mm 539042 MPL dims Figure 1 Gas...

Страница 6: ...lation and Figure 3 for additional information concerning installation heights construction details and methods of installation A location that requires cutting the least number of joists and rafters...

Страница 7: ...11CF4 4 ft pipe Maintain 2 Minimum Air Space Between Chimney and Combustibles Gas Line Optional Flexible Duct Type FP 4 U Combustion Air Assembly Optional Metal Safety Strip Floor Line Firestop Requi...

Страница 8: ...e surrounding walls chase should be insu lated Failure to insulate the fireplace from outside temperatures will cause heat loss through and around the fireplace INSTALLATION PREPARATION 14 Min FP2347...

Страница 9: ...does eventually develop the metal safety strip will serve as a barrier to prevent sparks or embers from falling from the fireplace onto combustible flooring materials NOTE If noncombustible hearth ex...

Страница 10: ...ontains two 11 diameter elbows One pair is required for each offset 11CS Chimney support required when chimney height exceeds 30 feet SLTCF11 Chimney cap for contemporary installations RLTCF11 Round c...

Страница 11: ...eplace it is very important to properly install the chimney This is an important part of the installation and the sections of this manual pertaining to chimney installation should be reviewed very tho...

Страница 12: ...10 FP2352 FP1890 chimney install Figure 13 Outer Pipe Flue Support Straps Fasten Securely Firestop Chimney Support Snap Lock Chimney Support Securely to Lower pipes Before Fastening Support Straps FP1...

Страница 13: ...you must use chimney support model 11CS at or below 30 feet to support the weight of additional chimney pipe To install the chimney support place the crimped end of the flue and outlet air duct portio...

Страница 14: ...uld be installed to provide the firestop and support required Be sure proper spacing in maintained between the chimney and combustibles CHIMNEY OFFSET INSTALLATION 3 Min FP2353 single story offset Fig...

Страница 15: ...y is measured from the hearth to the chimney exit MPL11 Max 86 0 Min 0 Elbows 14 0 2 Elbows 14 0 4 Elbows 21 0 B Do not use more than 4 elbows per chim ney Attach the straps of the return top elbow to...

Страница 16: ...e flashing and the chimney with mastic Leave some excess mastic at this area to be used in step eight NOTE Use pliers and wear gloves when performing step seven to minimize the danger of cutting your...

Страница 17: ...llar may be trimmed off 8 Slide the storm collar down snugly against the flashing until the excess mastic left in step six is forced up into the crack between the storm collar and the chimney This sho...

Страница 18: ...th the four sheet metal screws provided 3 Cut a 6 inch diameter opening for model AK 4 in the outside wall covering where the outside vent is to be located 4 Select and cut a piece of duct sufficient...

Страница 19: ...ver duct connector until an equal length of connector extends into each duct 3 Place duck clamp over the end of each duct Tighten duct clamp down snuggly 4 Push insulation back into place and over duc...

Страница 20: ...alling an ANSI Z21 11 2 ventless ap pliance the finishing material used for the mantel must be rated at 250 F or greater 2 An approved gas shut off valve must be located out side the fireplace in an a...

Страница 21: ...eplace Firebox Hearth Brick Gas Line Access Tube Repack Insulation Around Gas Line Where it Passes Through Gas Line Access Tube for Proper Seal Maintain 1 2 Minimum Air Space Clearance to Combustibles...

Страница 22: ...eet metal screws and place din the mortar joints of masonry trim Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the fireplace face Seal the f...

Страница 23: ...rally more expensive but a little combined with other wood goes a long way Start your fire with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods...

Страница 24: ...65 83 88 Spruce 41 44 59 Birch 55 64 79 86 Redwood 33 40 47 54 Apple 58 62 83 84 White Pine 35 37 50 A Few Words Of Caution Beware of burning certain material in your fireplace Among these are plastic...

Страница 25: ...heating season to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection main...

Страница 26: ...Do trim the face of the fireplace only with noncombustible materials 5 Do attach the noncombustible face trim material firmly to the face of the fireplace 6 Do block in or fasten the fireplace to pre...

Страница 27: ...ners near the fireplace 16 Don t neglect to instruct all responsible persons in the proper and safe operation of the fireplace 17 Don t fail to instruct all persons especially children and elderly per...

Страница 28: ...Assy 1 043006 4 Post Corner Ptd Assy 4 043008 5 Cap Corner Post 2 043009 6 Flange Nailing Ptd Assy 2 043104 7a Panel Firescreen w Pull 4 026398 7b Rod Curtain Rod 4 024508 7c Clip Screen Rod 2 043024...

Страница 29: ...29 87D0173 MPL11 Woodburning Fireplace...

Страница 30: ...30 MPL11 Woodburning Fireplace 87D0173...

Страница 31: ...local building code contains restrictions on the use of this fireplace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or aro...

Страница 32: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: