background image

13

87D0173

MPL11 Woodburning Fireplace

chiMNey iNStaLLatioN

1.  Lay  out,  cut  and  frame  openings  through  all  ceilings  and  the  roof  at  the  point  where  the  chimney  will  pass 

through. Unless the chimney is to be offset, the point where the center line of the chimney will pass through the 
ceiling and roof can be determined with a plumb line as shown in 

Figure 10

. The fireplace should be located in 

the planned installation position. After the center line is established and a nail is driven to mark the point, the 
opening can be cut if you are satisfied with the chimney location relative to ceiling and roof joists and/or any other 
obstructions. The roof  opening center line should be marked by driving a nail through the roof from underneath 
that will penetrate the roof and can be located from the rooftop. If the chimney is to penetrate a pitched roof, the 
hole in the roof must be rectangular instead of square and should be sized according to Table1.

2.  Install the firestop spacer as required from beneath the ceiling unless the space above is attic space. In an attic, 

the firestop spacer should be installed at the floor level of the attic. You must have joists or headers on all four 
sides of the spacer and use a minimum of four 8-penney nails to secure the spacer.

3.  To install the chimney sections, insert the male end of the flue, the smallest diameter pipe, into the flue outlet of 

the fireplace and press down until the snap locks engage. Continue the process, adding the chimney sections 
on top of each other until the chimney is at least six inches above the roof opening on all sided. As the chimney 
sections are installed, check each joint to make sure it is properly locked to the previous section. If additional 
strength of the outer pipe joints is desired, you may use two or three sheet metal screws placed through the area 
where the outer pipes overlap one another. To install these screws, drill a 1/8-inch diameter hole through the 
chimney sections, taking care not to penetrate the inner flue pipe.  

WarNiNg:

  Be very careful when drilling the 

holes into the outer pipe. The drill must not penetrate the inner stainless steel pipe.

Note:

  If you intend to have a total fireplace installation of more that 30 feet you must use chimney support model 

11CS at or below 30 feet to support the weight of additional chimney pipe.
To install the chimney support, place the crimped end of the flue and outlet air duct portions into the last section 
of chimney pipe. Push down until the outside or inlet air duct of the chimney support overlaps and snap locks the 
chimney support into the chimney section.
Nail the support straps tightly to a building frame member or ceiling joist as shown by 

Figure 14

. You must use at 

least two 8-penney nails per strap.

elbow installation

The following are important points that should be observed 
when installing elbows on the fireplace:
1.  The support straps of all elbows not installed directly on 

top of the fireplace should be nailed securely to the sur-
rounding structure. This allows the support strap to carry 
the weight of the chimney above the elbow and prevents 
this weight from breaking the elbow or chimney sections 
apart.

2.  Elbows  should  not  be  used  in  any  combination  that  in-

clines the chimney more than 30 degrees from vertical.

3.  The limitations on the quantity of elbows per chimney are 

as follows: If the total height of the fireplace and chimney 
is—13’  or  more  —  two  (2)  elbows  may  be  used  in  the 
chimney.  21’ or more — four (4) elbows may be used in 
the chimney.

4.  The inclined portions of chimneys that pass through liv-

ing spaces likely to be used for storage should be enclosed to avoid contact with and possible damage to the 
chimney. The minimum air space of 2” between the chimney and enclosing materials must be maintained.

5.  The length of the inclined portion of chimney between elbows must not exceed 6’ when unsupported or 20’ if the 

chimney is supported at 6’ intervals with support such as metal support straps.

6.  When enclosing the elbows and inclined portions of the chimney, enclosing materials must be installed vertically 

to maintain the required 2” minimum air space clearance to the chimney at the extremities of the offset.  It is 
recommended that enclosing material not follow the inclined portions of the chimney.

FP1893
30 elbow 
8/08

Figure 14

Inlet Air 
Pipe

Flue

All four (4) support straps must be nailed on to framing member 
around the elbow with a minimum of two (2) 8-Penny nails per 
strap

Note:

  Although  both  halves  of  the  elbow  set  may  have  tie 

straps, only the top half must be secured. The bottom elbow half 
is not required to be secured for added stabilization of pipe.

FP1893

Содержание MPL11

Страница 1: ...result To reduce the risk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact local building officials about r...

Страница 2: ...d be aware however that failure to install operate and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths injuries and...

Страница 3: ...eas Intended Product Usage The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with zero clearance to combustible building materials at the side and top sp...

Страница 4: ...located inside the fireplace The counterweighted damper is operated by simply pushing up to open or pulling down to close the damper When the fireplace is not in use the damper should be closed to pr...

Страница 5: ...3 mm 3056M 768 mm 3756M 946 mm 42 1067 mm 45 6M 1162 mm 36 914 mm 38 965 mm 23 584 mm 1 2 13 mm 14 6 378 mm 856O 216 mm 12 305 mm 24 610 mm 22 6M 578 mm 9 229 mm 12 305 mm 539042 MPL dims Figure 1 Gas...

Страница 6: ...lation and Figure 3 for additional information concerning installation heights construction details and methods of installation A location that requires cutting the least number of joists and rafters...

Страница 7: ...11CF4 4 ft pipe Maintain 2 Minimum Air Space Between Chimney and Combustibles Gas Line Optional Flexible Duct Type FP 4 U Combustion Air Assembly Optional Metal Safety Strip Floor Line Firestop Requi...

Страница 8: ...e surrounding walls chase should be insu lated Failure to insulate the fireplace from outside temperatures will cause heat loss through and around the fireplace INSTALLATION PREPARATION 14 Min FP2347...

Страница 9: ...does eventually develop the metal safety strip will serve as a barrier to prevent sparks or embers from falling from the fireplace onto combustible flooring materials NOTE If noncombustible hearth ex...

Страница 10: ...ontains two 11 diameter elbows One pair is required for each offset 11CS Chimney support required when chimney height exceeds 30 feet SLTCF11 Chimney cap for contemporary installations RLTCF11 Round c...

Страница 11: ...eplace it is very important to properly install the chimney This is an important part of the installation and the sections of this manual pertaining to chimney installation should be reviewed very tho...

Страница 12: ...10 FP2352 FP1890 chimney install Figure 13 Outer Pipe Flue Support Straps Fasten Securely Firestop Chimney Support Snap Lock Chimney Support Securely to Lower pipes Before Fastening Support Straps FP1...

Страница 13: ...you must use chimney support model 11CS at or below 30 feet to support the weight of additional chimney pipe To install the chimney support place the crimped end of the flue and outlet air duct portio...

Страница 14: ...uld be installed to provide the firestop and support required Be sure proper spacing in maintained between the chimney and combustibles CHIMNEY OFFSET INSTALLATION 3 Min FP2353 single story offset Fig...

Страница 15: ...y is measured from the hearth to the chimney exit MPL11 Max 86 0 Min 0 Elbows 14 0 2 Elbows 14 0 4 Elbows 21 0 B Do not use more than 4 elbows per chim ney Attach the straps of the return top elbow to...

Страница 16: ...e flashing and the chimney with mastic Leave some excess mastic at this area to be used in step eight NOTE Use pliers and wear gloves when performing step seven to minimize the danger of cutting your...

Страница 17: ...llar may be trimmed off 8 Slide the storm collar down snugly against the flashing until the excess mastic left in step six is forced up into the crack between the storm collar and the chimney This sho...

Страница 18: ...th the four sheet metal screws provided 3 Cut a 6 inch diameter opening for model AK 4 in the outside wall covering where the outside vent is to be located 4 Select and cut a piece of duct sufficient...

Страница 19: ...ver duct connector until an equal length of connector extends into each duct 3 Place duck clamp over the end of each duct Tighten duct clamp down snuggly 4 Push insulation back into place and over duc...

Страница 20: ...alling an ANSI Z21 11 2 ventless ap pliance the finishing material used for the mantel must be rated at 250 F or greater 2 An approved gas shut off valve must be located out side the fireplace in an a...

Страница 21: ...eplace Firebox Hearth Brick Gas Line Access Tube Repack Insulation Around Gas Line Where it Passes Through Gas Line Access Tube for Proper Seal Maintain 1 2 Minimum Air Space Clearance to Combustibles...

Страница 22: ...eet metal screws and place din the mortar joints of masonry trim Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the fireplace face Seal the f...

Страница 23: ...rally more expensive but a little combined with other wood goes a long way Start your fire with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods...

Страница 24: ...65 83 88 Spruce 41 44 59 Birch 55 64 79 86 Redwood 33 40 47 54 Apple 58 62 83 84 White Pine 35 37 50 A Few Words Of Caution Beware of burning certain material in your fireplace Among these are plastic...

Страница 25: ...heating season to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection main...

Страница 26: ...Do trim the face of the fireplace only with noncombustible materials 5 Do attach the noncombustible face trim material firmly to the face of the fireplace 6 Do block in or fasten the fireplace to pre...

Страница 27: ...ners near the fireplace 16 Don t neglect to instruct all responsible persons in the proper and safe operation of the fireplace 17 Don t fail to instruct all persons especially children and elderly per...

Страница 28: ...Assy 1 043006 4 Post Corner Ptd Assy 4 043008 5 Cap Corner Post 2 043009 6 Flange Nailing Ptd Assy 2 043104 7a Panel Firescreen w Pull 4 026398 7b Rod Curtain Rod 4 024508 7c Clip Screen Rod 2 043024...

Страница 29: ...29 87D0173 MPL11 Woodburning Fireplace...

Страница 30: ...30 MPL11 Woodburning Fireplace 87D0173...

Страница 31: ...local building code contains restrictions on the use of this fireplace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or aro...

Страница 32: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: