21
STRATA1
Minimum dimensions of flue terminal positions see fig 19
Dimension
Terminal Position
Balanced flue
Non room
room sealed
sealed
A
Directly below an opening, air
brick, windows etc. Not
Recommended.
300 mm
300 mm
B
Below gutters, soil pipes or
drain pipes
75 mm
75 mm
C
Below eaves
200 mm
200 mm
D
Below balconies or car port
roof. Not Recommended.
200 mm
200 mm
E
From a vertical drain pipe or
soil pipe
150 mm
150 mm
F
From an internal or external
corner
300 mm
200 mm
G
Above ground, intersecting
roof or balcony level
300 mm
300 mm
H
From a surface facing the
terminal
2000 mm
2000 mm
I
From a terminal facing the
terminal
2000 mm
2000 mm
J
From an opening in the car port
(e.g. door, window) into dwelling
1200 mm
1200 mm
K
Vertically from a terminal on the
same wall
1500 mm
1500 mm
L
Horizontally from a terminal on
the same wall.
300 mm
300 mm
M
From a vertical structure on the
roof
500 mm
N/A
N
Above intersection with roof
500 mm
150 mm
P
Directly above an opening,
300 mm
300 mm
air brick, window etc
Q
Horizontally to an opening,
500 mm
500 mm
air brick, window etc
15.0 flue terminal positions (contd)
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.