35 of 49
Locking
Display
Internal Code (bO)
Cause
91
EEPROM failure
92
Hardware failure of electronic circuit board
110
129
Activation of thermostats for underfloor heating
110
422
Locking because of over heating
113
506
Activation of flue gas sensor
133
102
Locking because of gas failure
151
Internal locking of circuit board
151
97
Flame at atart of reset phase
152
Failure in programming
153
259
Reset Button pressed when boiler not in fault
154
425
Flow temperature rising too rapidly or no circulation
160
83
On ignition necessary fan speed not achieved
160
282
Blocked Fan
161
110
Measured fan speed above upper limit
183
105
Circuit board in programming mode
Safety cut-off
Display
Internal Code (bO)
Cause
20
142
Short circuit in heating supply sensor
20
143
Heating supply sensor circuit open
40
144
Short circuit in heating return sensor
40
145
Heating return sensor circuit open
50
146
Short circuit in service water or water tank sensor
50
147
Service water or tank sensors circuit open
111
141
Flow temperature above temperature limit (90 °C)
119
140
Low Water Pressure
135
84
Quantity of fan revolutions not correct
154
401
Return temperature greater than flow temperature
154
433
At Supply and return too high
Service and Maintenance
Error Codes