Water side
The fully watercooled sections are joined by cast iron conical nipples, and distribution
of boiler
pipe fitted to the return ensures even the temperature distribution throughout the boiler.
The cast iron sections are to BS.1452 Grade 200 with 7 mm wall thickness. Return and
flow connections to heating system are provided by stub-pipes at the rear of the boiler.
Under no circumstances should the boiler be fired when its circulation volume is less than
a recommended minimum volume calculated according to the following formula:
The following table provides hydraulic resistances at various water volumes relativ to boiler
Dt flow/return. The difference between flow and return temperatures of the bolier should
not be greater than 20 C to provide convenient operating conditions in the boiler:
Boilers must be connected to a chimney by using the shortest possible connector which
should be insulated by mineral wool or similar material. The flue connector must rise at
Flue design
an angle from boiler to chimney of not less than 10º. Conditions creating high resistance
and chimney
to gas flow should be avoided in the flue connector. The flue outlet of the boiler should
installation
not support the weight of chimney.
The draft generated by the chimney should be capable of overcoming the chimney
resistance.
Chimney calculations should be carried out in compliance with the standards. Conditions
of existing chimney should be checked and proper precautions should be taken against
excessive cooling and condensation. Chimneys should be lined if necessary
Positive draught conditions must be avoided
Negative draught conditions should be contained within -3 mm wg. (30Pa) for optimum
boiler performance.
The following table shows typical flue gas volumes at gross flue temperature of 190°C and
ambient air temperature of 20°C.
146.9
528.9
MD9
300
139.9
503.8
109.2
393.1
MD8
262
122.2
439.9
128.3
461.9
MD7
223
104
374.5
70.5
253.9
MD6
181
85.8
309
90.1
324.4
MD5
144
67.2
241.8
51.4
185.1
kW
g/sec
kg/h
g/sec
MD4
105
49
176.3
TECHNICAL INFORMATION
Boiler type
Output
Flue gas volume
Light Oil
C02=13%
Natural gas G20
C02=9.5%
kg/h
l/s
252
Output
kW
=
∆
t=10
o
C
∆
t=15
o
C
∆
t=20
o
C
Type
Mi
ni
m
um
Ci
rc
ul
at
io
n
Wa
te
r
Fl
ow
Hy
dr
au
lic
R
esi
st
an
ce
Wa
te
r
Fl
ow
Hy
dr
au
lic
R
esi
st
an
ce
Wa
te
r
Fl
ow
Hy
dr
au
lic
R
esi
st
an
ce
l/s l/s kPa l/s kPa l/s kPa
MD
4 0.41 2.5 8.1 1.66 3.7 1.25 2.2
MD 5
0.58
3.42
16.0
2.28
7.2
1.71
4.1
MD 6
0.75
4.38
15.5
2.92
6.8
2.19
3.9
MD 7
0.88
5.33
20.6
3.53
9.2
2.65
5.2
MD
8 1.05 6.23 29.5 4.15 13.2 3.13 7.5
MD
9 1.19 7.14 39.0 4.76 17.4 3.57 9.8