ProCon Boiler Controller Commissioning Quick 

Reference Guide 

This sheet is intended as a quick reference guide and should be read in conjunction with the 
operating and maintenance manual for the boiler supplied by MHG Heating Ltd. 

Adjustment of the appliances controller can only be undertaken once power has been applied to 
the boiler and it has passed through its internal system checks. 

The level of parameter adjustment required will be dependent upon the age of the appliance and 
the required system control. 

All appliance operational mode adjustments and settings are undertaken via the unit control fascia. 

 

Legend 

Button Label 

Function 

Units  Defaults 

T1 RESET 

Resets indicated large flashing fault codes. Places 

the boiler into fault is no fault is present (E153) 

0-200 N/A 

T2 

HOT WATER 

(HWS) 

Activates HWS generation capability. Indicated on 

the screen by a dash beneath the 

icon. 

-  

T3 

MODE 

Adjusts the operating mode for the heating circuit. 

Ÿ

 

 

     

 

Ÿ

 

T4 HWS 

SETPOINT 

Hot water storage temperature adjustment.  

Only possible is a HWS sensor is used.  

20-60 55

o

T5 

HEATING 

CIRCUIT FLOW 

TEMPERATURE 

SETPOINT 

Heating flow temperature adjustment.  

Or 

Assumed room temperature adjustment.  

(If outside air sensor installed) 

20 – 90 

 

10 - 35 

80

o

 

21

o

Содержание ProCon Boiler Controller

Страница 1: ...quired will be dependent upon the age of the appliance and the required system control All appliance operational mode adjustments and settings are undertaken via the unit control fascia Legend Button...

Страница 2: ...m settings Fault Indication Boiler Flow Temperature Stored HWS Operation Mode Outside Air Temperature Legend Button Label Function 1 WATER PRESSURE INDICATOR Not used In ProCon Ranges 2 MAIN DISPLAY F...

Страница 3: ...on that is available To access these parameters the following sequence must be undertaken Press and release the INFO Press Hold the Program Buttons simultaneously for at least 3 second The display wil...

Страница 4: ...ode will be generated and displayed by the failing appliance and all LPB networked RVA and Opentherm units If a fault is encountered by a RVA controller or is communicated to a RVA controller via the...

Страница 5: ...perating at correct speed LMU Version D E 130 Flue Temperature Too High Auto Resetting E 131 Fault With Burner E 132 External Safety Interlock Activated Open Circuit E 133 No Flame Detected After Fina...

Страница 6: ...Signal Lost During Operation 99 Flame Signal Lost During Operation 100 Flame Signal Lost During Operation 101 Flame Signal Not Detected Following Last Ignition Attempt 102 Flame Signal Not Detected F...

Страница 7: ...or Program Buttons The display will now indicate Use the Program Buttons to access the desired parameter line Use the Button to alter the displayed parameter to the required setting To save the adjus...

Страница 8: ...ch 1 Third Off 00 00 24 00 Time Switch 2 Heating Zone 2 Set Points AGU2 500 Clip and QAD36 sensors required P20 Heating Circuit 2 Time Switch 2 Day Selection 1 2 1 5 1 7 1 7 P21 Heating Circuit 2 Time...

Страница 9: ...er winter changeover temperature 30 C S W changeover deactivated 8 30 C 18 18 18 18 H532 Heating curve slope heating circuit 1 1 40 32 32 32 32 H533 Heating curve slope heating circuit 2 1 40 1 1 1 1...

Страница 10: ...units 3 12 0 16 1 1 1 2 3 12 H606 LPB segment number of LMU 0 14 0 0 0 0 H614 Program input LMU basis 0 255 3 3 3 3 H615 Function programmable output K2 LMU 0 255 0 0 0 0 H618 Progr input on clip in...

Страница 11: ...umber of Occurrences H713 5th Historical Fault Operating Phase H714 5th Historical Fault Operating Error Code H715 Current Historical Fault Number of Occurrences H716 Current Historical Fault Operatin...

Отзывы: